TROUBLESHOOTING
EAGLEHAWK Controller Troubleshooting
The following LEDs of the EAGLEHAWK controller can be used for troubleshooting purposes:
Power
LED
(green)
Status LED (red)
L1 and L2 LEDs (yellow)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs
Power LED (green) of EAGLEHAWK
Table 21. EAGLEHAWK controller power LED
case power LED
meaning
remedy
1
ON
Normal operation
No action necessary.
2
OFF
Power supply not OK.
►
Check power supply voltage.
►
Check wiring.
►
If problem persists, replace hardware.
Status LED (red) of EAGLEHAWK
Table 22. EAGLEHAWK controller status LED
case status LED
meaning
remedy
1
OFF after
power-up
Normal operation.
No action necessary.
2
ON con-
tinuously after
power-up
– No or invalid firmware, or
– No or corrupt application.
►
Try powering down and then powering up the
EAGLEHAWK controller.
►
If problem persists, replace hardware.
L1 LED
Table 23. EAGLEHAWK controller bus L1 LED
case bus LEDs
meaning
remedy
1
ON con-
tinuously after
power-up
Normal operation; this may continue for
several minutes until the platform is running
No action necessary.
2
Flashes
constantly
The platform is running
No action necessary.
3
Dark
Severe software problems.
►
Contact TAC.
L2 LED
Table 24. EAGLEHAWK controller bus L2 LED
case bus LEDs
meaning
remedy
1
ON con-
tinuously after
power-up
Station is starting up. It may take several
minutes until the station is ready to
communicate.
No action necessary.
►
If you are unable to establish communication,
consult "Application Director Output" in COACH
AX
.
2
Dark
Station is not running
►
Contact TAC.