25
MAN0604_Issue 09_02-2013
Apex
2110M8030
3. inSTAllATiOn
3.1.2 Fitting the Certified Sensor
(1)
Fit the Certified Sensor to the Transmitter Unit.
Feed the sensor cable through the Certified Sensor mounting point at the front of the
Transmitter Unit base. Screw the sensor firmly into the mounting point until it is fully home.
(2)
Connect the sensor wiring.
See the following wiring table and diagram.
Terminal
Function
Colour
Recommended
Number
Wire Length
SK3
1
CAN_L
White
40mm
(Sensor)
2
CAN_H
Green
40mm
3
+V
Red
40mm
4
0V
Black
40mm
5
Screen
40mm
SK4
1
NET1
60mm
(Comms
2
NET2
60mm
and
3
Ground
50mm
Power)
4
4 - 20mA -
50mm
5
4 - 20mA +
50mm
6
0V
50mm
7
+24Vdc (18-32Vdc)
50mm
SK6
1
Fault
50mm
(Relays)
2
Fault common
50mm
3
Alarm 1
50mm
4
Alarm 1 common
50mm
5
Alarm 2
50mm
6
Alarm 2 common
50mm
g
- Earth
Green/Yellow
Certified Sensor
mounting point
Certified Sensor
Transmitter Unit
base