113
MAN0604_Issue 09_02-2013
Apex
2110M8030
A.4 LONWORKS COMMUNICATIONS BOARD
When fitted to a Transmitter Unit the LonWorks communications board provides an interface
between the unit and an open LON standard network.
The board consists of a Neuron micro-processor and associated memory and logic interface
components. Isolation to the network and correct signal levels are provided by an FTT-10A
transceiver device.
A.4.1 LonWorks Network Variables
The
LIFELINE II
gas detector has fourteen Network variable outputs, two network variable inputs
and four network configuration inputs as shown in the following LonMark Object Diagram.
Some or all of these may be bound to a LonWorks network. Descriptions of each variable are given
in the subsequent sub-sections. For more information consult Honeywell Analytics.
nviRequest
nvoFaultD
nvoFaultS
nvoStatus
Node Object
nviResetAlm
nvoAlm2
nvoAlmL
nvoAlmThresh1
nvoAlmThresh2
nvoCellLife
nvoCellType
nvoConc
nvoConcFS
nvoConcType
nvoLastCal
nvoNextCal
Open-Loop Sensor Object
nciAlarmSetT
nciHighLim1
nciHighLim2
nciMaxSendT
Virtual Function Block
(SNVT_lev_disc)
(SNVT_lev_disc)
(SNVT_lev_disc)
(SNVT_ppm_f)
(SNVT_lev_disc)
(SNVT_obj_request)
(SNVT_switch)
(SNVT_obj_status)
(SNVT_ppm_f)
(SNVT_ppm_f)
(SNVT_ppm_f)
(SNVT_elapsed_tm)
(SNVT_ppm_f)
(SNVT_elapsed_tm)
(SNVT_elapsed_tm)
(SNVT_str_asc)
(SNVT_str_asc)
(SNVT_ppm_f)
(SNVT_elapsed_tm)
(SNVT_elapsed_tm)
LIFELINE II
Gas Detector
APPENDIX A - SPECIFICATIONS
LonMark Object Diagram