7847i/7847i-E Installation and Setup Guide
3-18
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY OPTIONS
DESCRIPTION
47
Restore Zn3 Y/N
(Y)_
✔
✔
[Y], [N]
Enables restore reporting for zone 3.
48
Delay Zn3 (secs)
(00)
✔
✔
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 3.
49
Rpt Zn3 ONLY if
Armed (N)_
✔
✔
[Y], [N]
Reports alarms on zone 3 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered
(armed).
If [N], always reports alarms on zone 3.
4204 mode:
If any zone is programmed to "Report
Only if Armed," skip to Prompt 60: "Enable Zn6."
50
Zn4 Trigger Type
(V+)_
✔
•
(EOLR)
•
(V+)
•
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
51
Invert Zn4 Y/N
(N)_
✔
[Y], [N]
Inverts the alarm and normal states of the zone 4
trigger; otherwise uses normal input signal.
52
Restore Zn4 Y/N
(Y)_
✔
✔
[Y], [N]
Enables restore reporting for zone 4.
53
Delay Zn4 (secs)
(00)
✔
✔
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 4.
54
Rpt Zn4 ONLY if
Armed (N)_
✔
2-
4204
only
[Y], [N]
Reports alarms on zone 4 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-
4204 mode) is triggered (armed).
If [N], always reports alarms on zone 4.
55
Zn5 Trigger Type
(V+)_
✔
•
(EOLR)
•
(V+)
•
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
56
Invert Zn5 Y/N
(N)_
✔
[Y], [N]
Inverts the alarm and normal states of the zone 5
trigger; otherwise uses normal input signal.
57
Restore Zn5 Y/N
(Y)_
✔
2-
4204
only
[Y], [N]
Enables restore reporting for zone 5.
58
Delay Zn5 (secs)
(00)_
✔
2-
4204
only
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 5.
59
Rpt Zn5 ONLY if
Armed (N)_
✔
2-
4204
only
[Y], [N]
Reports alarms on zone 5 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-
4204 mode) is triggered (armed).
If [N], always reports alarms on zone 5.
60
Enable Zn6 Y/N
(N)_
4204
only
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 66: "Enable Zn7."
61
Zn6 Trigger Type
(V+)_
✔
4204
only
•
(EOLR)
•
(V+)
•
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
62
Invert Zn6 Y/N
(N)_
✔
4204
only
[Y], [N]
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Содержание AlarmNet 7847i-E
Страница 2: ......
Страница 14: ...7847i 7847i E Installation and Setup Guide 2 6 ...
Страница 42: ...7847i 7847i E Installation and Setup Guide 5 4 ...
Страница 52: ...7847i 7847i E Installation and Setup Guide B 2 ...
Страница 56: ...7847i 7847i E Installation and Setup Guide D 2 ...
Страница 57: ...NOTES ...
Страница 58: ...7847i 7847i E Installation and Setup Guide NOTES ...
Страница 59: ...NOTES ...
Страница 60: ...7847i 7847i E Installation and Setup Guide NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...7847i 7847i E Installation and Setup Guide NOTES ...