Section 3: Programming the 7847i/7847i-E
3-9
ECP Status Codes
When the 7847i/7847i-E is configured for ECP mode, it sends status messages to the control
panels (e.g., VISTA-10P, VISTA-15P and VISTA-20P Series), for tamper, and network
connectivity failures. Some of the control panels display these on the keypad as "LngRng
Radio" followed by a 4-digit code (listed in table 4). In addition, the Contact ID codes (listed
in Appendix B) for these conditions are sent to the central station by the module.
Table 4. Common ECP Keypad Displays Status Codes
STATUS CODE
DESCRIPTION
0000
Control panel lost communication
with 7847i/
7847i-E.
0880 7847i/7847i-E
tamper
detected (cover removed).
0005
7847i/7847i-E has lost Ethernet connectivity.
000F 7847i/7847i-E
is not registered; account not activated.
0019 7847i/7847i-E
shutdown.
0400 7847i/7847i-E
power
on reset AND the control panel lost communications
with 7847i/7847i-E.
0C80 7847i/7847i-E
power
on reset AND tamper detected.
0C8F 7847i/7847i-E
power
on reset AND tamper detected AND not registered.
Alternative Modes (Zone Trigger, 4204 and Two-4204)
Zone Trigger Mode
There are six input zones available on the 7847i/7847i-E. Zones 1 and 2 are located on TB1
pin 5
and are selectable for +V, -V, or EOLR modes, which can detect both pulsed and steady
signals. The pulsed signal is reported as an alarm on zone 1 (Fire); the steady signal is
reported as an alarm on zone 2 (Burg). The implied pulse count for zone 1 is fixed to 3
pulses. The unit
can be programmed to detect a single pulse on the input, characteristic of a
Panic indication on the Lynx Control Panel. If the programming option “Lynx Panic” is
enabled, the unit
reports an alarm on zone 3 when it detects this single pulse. No restores
are reported for this zone.
Zones 3, 4, 5, 6 and 7 are voltage trigger inputs located on TB1 pins 6-10. If the Lynx Panic
feature is being used, do not connect zone 3.
4204 Emulation Mode
In the 4204 Emulation Mode, the 7847i/7847i-E
communicates with a compatible Honeywell
VISTA series or First Alert control panel as though it were a 4204 Relay Module.
If the Two
4204 Mode is enabled in the module, it acts as two 4204s at consecutive device addresses.
The control panel must be configured to recognize one or two 4204 relay modules accordingly.
On VISTA-32FB (or higher) control panels and First Alert equivalents, addresses 6 and 13
should not be used when the secondary 4204 is enabled. Messages are sent in Honeywell
High-Speed format.
NOTE:
See your control panel Installation and Setup Guide for the number of 4204 modules supported.
The LynxR-I does not support 4204 mode.
4204 Emulation Mode Options
For control panels that do not support ECP communication, the 4204 Emulation modes
provide a means of sending up to eight unique reports based on defined system conditions. In
4204 mode, the 7847i/7847i-E
functions as a logical 4204 Relay Module, where each relay
number, referred in the module as zone number, can be programmed to send a report based
on the output function programmed in the control for that relay.
Each relay-zone can also be
programmed to send a restore message of the reported condition, can be set to delay
Содержание AlarmNet 7847i-E
Страница 2: ......
Страница 14: ...7847i 7847i E Installation and Setup Guide 2 6 ...
Страница 42: ...7847i 7847i E Installation and Setup Guide 5 4 ...
Страница 52: ...7847i 7847i E Installation and Setup Guide B 2 ...
Страница 56: ...7847i 7847i E Installation and Setup Guide D 2 ...
Страница 57: ...NOTES ...
Страница 58: ...7847i 7847i E Installation and Setup Guide NOTES ...
Страница 59: ...NOTES ...
Страница 60: ...7847i 7847i E Installation and Setup Guide NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...7847i 7847i E Installation and Setup Guide NOTES ...