Start Output Device Mapping by pressing *79 while in Data Programming Mode.
∗∗∗∗
79 Output Device Menu Mode
ENTER OUTPUT NO.
00 = QUIT
xx
Device Output Number
01-18 = relays/X-10
[
∗
] to continue; 00 to quit
This is the logical (or reference) relay number as used in the system. Relays and X-10
devices are numbered 01-16; the on-board triggers are numbered 17 and 18 and can be
programmed for inverted output, if required.
17 OUT NORM LOW
0 = NO 1 = YES
0
Output Normally Low
(prompt appears only for Triggers 17 and 18)
0 = no (standard default); 1 = yes
[
∗
] to continue
Selecting
0
(no) sets the output level normally high (default setting).
Selecting
1
(yes) sets the output normally low.
Output Trigger 17 can be used for resetting 4-wire smoke detectors
†
by connecting it to the
negative power terminal of the smoke detector, selecting 1 at this prompt, and setting as
zone type 54, fire zone reset, in *80 Menu mode.
After entry, display returns to Output Number prompt. Use *80 Menu mode to program
the function of the trigger.
†
Power Reset:
This control does not automatically reset power to 4-wire smoke detector
zones, so you must use a relay (e.g., 4204, 4229) or on-board trigger to reset power (also
required for fire verification).
XX OUTPUT TYPE
DELETE 0
Output Type
0 = delete; 1 = relay on 4204/4229 module; 2 = Powerline Carrier device (X-10)
[
∗
] to continue
Select whether this is a relay or a Powerline Carrier (X-10) device.
If Powerline Carrier is selected, go to “A” prompt.
If relay is selected, skip to “B” prompt.
“
A
”
XX UNIT No.
yy
Unit Number
(
prompt appears
if X-10 is selected)
01-16 = predefined address
[
∗
] to continue
Enter the unit code (set at the device) and press [
∗
].
The system returns to the Output Number prompt.
“
B
”
XX MODULE ADDR
07-15 yy
Module Address
(
prompt appears
if relay is selected)
07-15 = predefined address
[
∗
] to continue
Enter the predefined address for this module as listed below. Make sure the module’s DIP
switches are set to the selected address.
NOTE:
If using Multi-Mode (IP/GSM feature), select one of the 4204 addresses, though a
physical 4204 module is not installed. If using 2-4204 multi-mode option, the second 4204
address is automatically one number higher than the first one selected. Make sure these
addresses are not used by physical 4204 modules that may be installed. If using Multi-
Mode Enhanced Reports option, RIS must be enabled in field *91; when enabled, address
25 is automatically assigned. See
∗
29 Menu Mode section for enabling Multi-Mode.
Module Addresses
Address Module
07
1st 4229 (with zones 09-16)
08
2nd 4229 (with zones 17-24)
09
3rd 4229 (with zones 25-32)
10
4th 4229 (with zones 33-40)
11
5th 4229 (with zones 41-48)
12
1st 4204
13
2nd 4204
14
3rd 4204
15
4th 4204
Installation and Setup Guide
5-10
Содержание Ademco VISTA-21iPSIA
Страница 26: ...Installation and Setup Guide 2 20 ...
Страница 78: ...Installation and Setup Guide 6 8 ...
Страница 84: ...Installation and Setup Guide 8 4 ...
Страница 88: ...Installation and Setup Guide 9 4 ...
Страница 89: ...Notes 9 5 ...
Страница 90: ...Notes Installation and Setup Guide 9 6 ...