*69
Recent Closing Report
V21iPSIA only
Always enabled. Field does not apply to other controls.
Similar to the Exit Error condition described in field
*59, but occurs if any burglary zone is faulted within
two minutes
after
the initial exit delay expires.
Disarming the system within the two minutes stops the
alarm sound and displays "ALARM CANCELED " or
"CA" and the faulted zone number. No message is sent
to the Central Monitoring Station.
If the system is not disarmed within two minutes, the
alarm sound continues and a “recent closing” and a
“zone alarm” message are sent to the Central
Monitoring Station (after dial delay expires).
*70
Alarm Restore Report Code
0 = no report; 1-F = see description above *59
See UL System Reporting Note above *59.
Alarm restore signals indicate that respective alarm
zone(s) are no longer faulted. Alarm restore reports are
sent to the central station at bell timeout (field *33), if
the zone(s) in alarm are actually restored to a non-
faulted state at that time. Otherwise, alarm restore
report(s) for respective alarm zones are sent when the
system is disarmed.
*71
Trouble Restore Report Code
0 = no report; 1-F = see description above *59
Sent when a zone trouble is restored and code + OFF
performed. See UL System Reporting Note above *59.
*72
Bypass Restore Report Code
0 = no report; 1-F = see description above *59
Sent when a zone that has been bypassed is
unbypassed. See UL System Reporting Note above *59.
*73
AC Restore Report Code
0 = no report; 1-F = see description above *59
Sent after AC power has been restored after an AC power
outage. See UL System Reporting Note above *59.
*74
Low Bat Restore Report Code
0 = no report; 1-F = see description above *59
Sent after a system low-battery condition is restored to
normal. See UL System Reporting Note above *59.
*75
RF Xmtr Low Batt. Restore Code
0 = no report; 1-F = see description above *59
Sent when a transmitter’s low battery condition is
restored (i.e., new battery installed).
UL: must be enabled if wireless devices are used. See
UL System Reporting Note above *59.
*76
Test Restore Report Code
0 = no report; 1-F = see description above *59
This is sent when the Test mode is exited or upon
timeout. See UL System Reporting Note above *59.
Miscellaneous System Fields
*77
Daylight Saving Time Start/End Month
0 = Disabled; 1 = Jan; 2 = Feb; 3 = Mar; 4 = April;
# + 10 = Oct; # + 11 = Nov; # + 12 = Dec
Enter the start and end month for daylight saving time,
if applicable to the region.
*78
Daylight Saving Time Start/End Weekend
0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth;
5 = last; 6 = next to last; 7 = third to last
Enter the start and end weekend for daylight saving
time, if applicable to the region.
*79
Output Device Mapping Menu Mode
Use this menu mode to enter output devices/powerline
carrier devices into the system. See Output Device
Programming section for procedures.
*80
Output Programming Menu Mode
Use this menu mode to define output functions for use
with output devices/powerline carrier devices. See
Output Programming section for procedures.
*81
Zone List Programming Menu Mode
Use the menu mode to define zone lists. See Zone List
Programming section.
*82
Alpha Descriptor Programming Menu Mode
Use this menu mode to assign alpha descriptors to
zones and/or create partition descriptors.
*84
Auto-Stay Arm
0 = no; 1 = partition 1 only; 2 = part. 2 only; 3 = both parts.
If enabled, the system will automatically change AWAY
mode to STAY mode if the entry/exit door
is not
opened
and closed within the exit delay time after a user arms
in AWAY mode from a wired keypad (non-RF device).
An Opening report followed by an Armed Stay report is
sent to the Central Station.
If the door
is
opened and closed within the exit delay
period, the system remains in AWAY mode.
Any RF device that arms the system AWAY overrides
this feature and the system remains armed AWAY.
*85
Cross Zone Timer
0 = 15 secs 4 = 90 secs
8 = 4 min
#+12 = 8 min
1 = 30 secs 5 = 2 min
9 = 5 min
#+13 = 10 min
2 = 45 secs 6 = 2-1/2 min #+10 = 6 min #+14 = 12 min
3 = 60 secs 7 = 3 min
#+11 = 7 min #+15 = 15 min
Sets the maximum amount of time in which two cross
zones must be tripped in an armed system to send an
alarm message to the Central Station. If only one cross
zone is tripped during this time, a trouble message (CID
code 380) for that zone is sent to the Central Station.
Assign cross zone pairs in zone list 4.
This option not for use in UL installations.
NOTE:
Cross zoning takes effect only after Exit Delay
expires.
*86
Cancel Verify Keypad Display
0 = no
“
alarm canceled
”
display
1 = display
“
Alarm Canceled
”
when system is disarmed
after an alarm has occurred. (To clear the
“
ALARM
CANCELED
”
display, the user must enter the security
code + OFF again.)
This feature causes a “
ALARM CANCELED
”
display on
the LCD keypad under the following conditions:
•
After the kissoff of the cancel message to the Central
Station, indicating a successful transmission.
•
When an alarm is successfully canceled before the
Central Station received the Alarm message. E.g., if
an alarm is incorrectly triggered and the user presses
code + OFF before the dial delay time has expired, the
message will never go out to the CS.
•
When the Cancel report is not enabled and the system
is disarmed:
a.
before
dialer delay expires (alarm report not sent)
message “Alarm Canceled” is displayed.
b.
after
dialer delay expires message “Alarm
Canceled” is not displayed.
Data Field Programming
4-5
Содержание Ademco VISTA-21iPSIA
Страница 26: ...Installation and Setup Guide 2 20 ...
Страница 78: ...Installation and Setup Guide 6 8 ...
Страница 84: ...Installation and Setup Guide 8 4 ...
Страница 88: ...Installation and Setup Guide 9 4 ...
Страница 89: ...Notes 9 5 ...
Страница 90: ...Notes Installation and Setup Guide 9 6 ...