Extinguishing Control Computer 8010 - Series 2
FB 798352 / 11.07
75
12.9 Resetting the panel 8010
The Extinguishing Control Computer 8010 can be reset via the function key of the control panel. For operation,
the keypad must be enabled via the key-switch. To restart the system press the appropriate button. The internal
panel status and all visual displays will be resetted.
For deactivated zones or zones in >Test mode< the restart does not take affect.
Un-
locked
K
ey
bo
ard Rele
as
e
Panel reset
In operation
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Emergency release
Extinguishing system
activated
Extinguishing system
enabled
Fig. 15: Operating example – panel reset
12.10 Lamp test
The lamp test can be carried out via the keypad. For operation, the keypad must be enabled via the key-switch.
All visual displays of the control panel lights up and the control panel buzzer is activated until the key is
released.
Lamp test
1
2
3
4
5
6
7
8
9
10 11 12 13
Detector zone
Fire/Switch off/Trouble
Un-
locked
K
ey
bo
ard Rele
a
s
e
In operation
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Emergency release
Extinguishing system
activated
Extinguishing system
enabled
Common trouble
Emergency
operation
Power trouble
Battery trouble
Ground fault
Trouble 1
Blocking
Fig. 16: Operating example – Lamp test