12.2 Operating displays
The operating displays give a quick overview of the current state of the Extinguishing Control Computer 8010.
In operation
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Emergency release
Extinguishing system
activated
Extinguishing system
enabled
Fig. 4: Operating display
Operation (green LED)
On
Î
System ready for operation, keypad locked.
Flashes
Î
System ready for operation, keypad enabled for operation with the key switch.
Off
Î
Failure of the mains and emergency power supply.
Extinguishing system enabled (red LED)
On
Î
The connected extinguishing system has been enabled.
An evacuation time is started. After the evacuation time expires, release is initiated unless it
is stopped or prevented manually. The evacuation time is programmable between 1 to 255
seconds.
Extinguishing system activated (red LED)
On
Î
The enabled extinguishing system has been activated.
The flooding function is carried out and the extinguishing agent is released. Disconnection
of the activated extinguishing system is not possible.
Depending on the system configuration a new flooding may be carried out by pressing the
extra release button.