Emergency Stop (yellow LED)
On
Î
An already triggered extinguishing procedure is stopped during the evacuation time by the
Emergency Stop zone 10.
An emergency stop button of this technical zone has been pressed.
Switch-off (yellow LED)
On
Î
Common disablement, at least one disablement was recognized.
Test operation (yellow LED)
On
Î
The test operation of an detector zone was activated.
The Test Mode function can only be activated one automatic detector zone no.1-8 at the
same time.
Flashes
Î
The revision mode for outputs has been activated. The function >Revision mode< is
activated for all outputs which have been programmed with the revision function.
Revision mode always has priority over the test mode in the display!
Extra releasing (green LED)
On
Î
The LED indicates that the post-flooding has been triggered by the manual detector zone
(if configured as a common detector zone) or the extra released zone no. 11 has been
activated after the flooding time.
Outputs ( green LED)
On
Î
Indicates that an output has been triggered.
Additional information is given by the yellow LED in the status display of the outputs.
Alarm (red LED)
On
Î
Common fire
Î
at least one fire message was detected.