44
02.13
Input terminal DI1 function
0
~
30
3
02.14
Input terminal DI2 function
0
~
30
4
02.15
Input terminal DI3 function
0
~
30
0
02.16
Input terminal DI4 function
0
~
30
0
02.17
Input terminal DI5 function
0
~
30
0
0: Reserved
1: Forward jog control
If the terminal is short-circuited with GND, the inverter will run in forward jog mode, which is only valid when 00.02=1.
2: Reverse jog control
If the terminal is short-circuited with GND, the inverter will run in reverse jog mode, which is only valid when 00.02=1.
3: Forward running (FWD)
If the terminal is short-circuited with GND, the inverter will run forward, which is only valid when 00.02=1.
4: Reverse operation (REV)
If the terminal is short-circuited with GND, the inverter will run in reverse, which is only valid when 00.02=1.
5: Three-line operation control
Refer to 02.18 for the function description of operation mode 2, 3, 4 (three-wire control mode 1, 2, 3).
6: Free stop control
This function has the same meaning as the free-running stop defined in 01.04, but here is realized by the control terminal, which is convenient for remote control.
7: External stop signal input (STOP)
This function is used in emergency stop situations, the terminal is short-circuited with GND, and the stop is decelerated by the deceleration time (00.11).
8: External reset signal input (RST)
When a fault occurs in the inverter, the fault can be reset through this terminal. Its function is the same as that of the key
S T O P / R E S E T
. This function is valid under
any command channel.
9: External equipment failure normally open input
Through this terminal, the fault signal of the external equipment can be input, which is convenient for the inverter to monitor the fault of the external equipment.
After the inverter receives the external equipment failure signal, it will display "E-EF", that is, the external equipment failure alarm, and the failure signal can adopt the
normally open input mode.
10: Frequency increment command
When the terminal is short-circuited with GND, the frequency will increase. It is valid only when the frequency setting channel is digital setting 2 (terminal
UP/DOWN adjustment).
11: Frequency decreasing instruction
If the terminal is short-circuited with GND, the frequency will decrease. It is valid only when the frequency setting channel is digital setting 2 (terminal UP/DOWN
adjustment).
13: Multi-speed selection S1
14: Multi-speed selection S2
15: Multi-speed selection S3
By selecting the ON/OFF combination of these function terminals, up to 7 speeds can be selected. The details are shown in the following table:
S3
S2
S1
Stage speed
OFF
OFF
ON
1