60
0
:
Broadcast address.
1
~
247
:
Slave
06.01
MODBUS communication configuration
0000
~
0322
0000
LED bit
:
baud rate selection
0
:
9600BPS
1
:
19200BPS
2
:
38400BPS
This function code is used to define the data transmission rate between the host computer and the inverter. The baud rate set by the host computer and the
inverter should be the same, otherwise the communication cannot be carried out. The larger the baud rate setting, the faster the data communication. Setting the
conference too much affects the stability of communication.
LED ten bits
:
data format
0
:
no parity
1
:
even parity check
2
:
Odd Parity Check
The data format set by the host computer and the inverter should be consistent, otherwise normal communication will not be possible.
Hundreds of LEDs: Communication response method
0: normal response
1: Only respond to the slave address
2: No response
3: The slave does not respond to the free stop command of the master in the broadcast mode
Thousands of LEDs: reserved
06.02
Communication timeout check-out time
0.1
~
100.0s
10.0s
If the machine does not receive the correct data signal within the time interval defined by this function code, then the machine thinks that the communication has
failed, and the frequency inverter will decide whether to protect or maintain the current operation according to the setting of the communication failure action mode;
When this value is set to 0.0, RS485 communication timeout detection is not performed.
06.03
local device response delay time
0
~
200ms
5ms
This function code defines the intermediate time interval between receiving the data frame of the inverter and sending the response data frame to the upper
computer. If the response time is less than the system processing time, the system processing time shall prevail.
06.04
Proportional linkage coefficient
0.01
~
10.00
1.00
This function code is used to set the weight coefficient of frequency instruction received by inverter as slave through RS485 interface, and the actual operating
frequency of this machine is equal to the value of this function code multiplied by the value of frequency setting instruction received through RS485 interface. In the
linkage control, this function code can set the ratio of operating frequency of multiple inverters.
06.05
Multi-vendor agreement selection (reserved)
0
~
3
0