39
Figure 01-4 Schematic diagram of PLC shutdown after a single cycle
1: Continuous circulation
After the inverter completes a cycle, it will automatically start the next cycle, and will not stop until a stop command is issued. As shown below:
Figure 01-5 PLC continuous cycle diagram
2: Keep the final value after a single cycle
After the inverter completes a single cycle, it automatically maintains the operating frequency and direction of the last segment to operation. As shown below:
Fig. 01-6 The schematic diagram of PLC holding after a single cycle
Hundreds of LEDs: start mode
0: restart from the first segment
Stop during operation (caused by stop command, fault or power failure), and start to run from the first stage after restart.
1: Start from the stage at the moment of shutdown (fault)
If the inverter stops during operation (caused by a stop command, fault or power failure), the inverter will automatically record the running time of the current stage.
After restarting, it will automatically enter this stage and continue to run for the remaining time at the frequency defined in this stage, as shown in the figure below: