37
Fig. 01-1 Schematic diagram of starting DC braking
01.04
Stop mode
0
~
1
0
0: Decelerate to stop
After receiving the stop command, the inverter will gradually reduce the output frequency according to the deceleration time, and stop after the frequency drops
to zero. If the stop DC braking function is valid, after reaching the start frequency of the stop DC braking (according to the 01.05 setting, there may be a waiting time for
the stop DC braking), the DC braking process will be executed and the machine will stop.
1: Free stop
After the inverter receives the stop command, it immediately terminates the output, and the load stops freely according to the mechanical inertia.
01.05
Start frequency of DC braking during stop
0.0
~【
00.05
】
upper limit frequency
0.00
01.06
Stop DC braking Voltage
0.0
~
150.0
%
* rated Voltage of motor
0.0%
01.07
Time for DC braking during stop
0.0
~
30.0S
0S
01.08
Waiting time for DC braking during stop
0.0:DC braking does not work
0.1
~
99.99s
0.0
The set value of the stop DC braking current is the percentage relative to the rated current of the inverter. When the braking time at stop is 0.0s, there is no DC
braking process. As shown below.
Fig. 01-2 Schematic diagram of DC braking at stop
01.09
Forward jog frequency
0.00
~【
00.05
】
10.00
01.10
Reverse jog frequency
0.00
~【
00.05
】
10.00
01.11
Jog acceleration time
0.1
~
999.9s
Model setting