Status and Diagnostics 8-3
© 2005 HMS Industrial Networks
AB7665 User manual
Ethernet Module Status LED
Ethernet Network Status LED
State
Summary
Description
Off
No Power
Not powered
Solid Green
Normal
The module is operating correctly.
Flashing Green
Standby
The module has not been initialized.
Solid Red
Unrecover-
able fault
A fault the requires user intervention
has been detected. Correct the problem
and reset the Anybus-X.
Flashing Red
Recoverable
fault.
A fault that can be corrected and does
not require a Anybus-X reset has been
detected.
Red,Green
Alternate Flashing
Self Test
A self test of the module is in progress.
Table 8-3 Ethernet Module Status LED States
State
Summary
Description
Off
No Power
The module has no power or no IP
address assigned.
Solid Green
Network OK
and commu-
nicating
There is at least one EtherNet/IP con-
nection.
(Not affected by Modbus/TCP
connections.)
Flashing Green
Network OK
There are no active connections.
(Not
affected by Modbus/TCP connections.)
Solid Red
Address con-
flict
The module’s IP address is already in
use by another module.
Flashing Red
Connection
Time-out
One or more of the connections in
which this module is the target has
timed out. This state is only left if all
timed out connections are re-estab-
lished or if the module is reset.
Red,Green
Alternate Flashing
Self Test
A self test of the module is in progress.
Table 8-4 Ethernet Network Status LED States