38 (124)
Setting
Value
57600 baud
115200 baud
128000 baud
Data bits
Data bits is the number of bits used in the data representation of characters in the telegrams.
The rate for Modbus RTU is 8 data bits and can not be changed.
Parity
Specify if parity should be used to detect errors in the data.
3.
Select
parity
value from the
Parity
drop-down menu.
Setting
Value
Description
Parity
None | Default value
No parity checking
Parity bit is not transmitted
Odd
Odd parity checking
Even
Even parity checking
Stop bits
Specify the number of stop bits used to indicate the end of data transmission.
4.
Select a
stop bits
value from the
Stop bits
drop-down menu.
Setting
Value
Stop bits
1 stop bit | Default value
2 stop bit
Apply configuration
5.
To apply the settings, click
Apply
in the web-interface header, and follow the instructions.
7.5.3
Communication Advanced Settings
Inter-Telegram Timeout Mode Settings
By default, Inter-telegram timeout mode Default (3.5 characters) is used.
This is according the Modbus RTU standard, which advocates the use of a silent period
equivalent to 3.5 characters between each message. The silent period is used to find out where
one message ends and the next begins.
Anybus
®
Communicator
™
User Manual
SCM-1202-152 1.10 en-US