Parameter Settings for Keypad Entry
Appendix C
C–4
A031
Multi-speed 11 setting
0.0
0.0
A032
Multi-speed 12 setting
0.0
0.0
A033
Multi-speed 13 setting
0.0
0.0
A034
Multi-speed 14 setting
0.0
0.0
A035
Multi-speed 15 setting
0.0
0.0
A038
Jog frequency setting
1.00
1.00
A039
Jog stop mode
00
00
A042
Manual torque boost value
5.0
5.0
A242
Manual torque boost value, 2nd
motor
0.0
0.0
A043
Manual torque boost frequency
adjustment
3.0
3.0
A243
Manual torque boost frequency
adjustment, 2nd motor
0.0
0.0
A044
V/f characteristic curve selection
02
02
A244
V/f characteristic curve selec-
tion, 2nd motor
02
02
A045
V/f gain setting
100.
100.
A046
Automatic torque boost voltage
gain
100
100
A246
Automatic torque boost voltage
gain, 2nd motor
100
100
A047
Automatic torque boost slip gain
100
100
A247
Automatic torque boost slip gain,
2nd motor
100
100
A051
DC braking enable
00
00
A052
DC braking frequency setting
0.5
0.5
A053
DC braking wait time
0.0
0.0
A054
DC braking force for deceleration
0
0
A055
DC braking time for deceleration
0.0
0.0
A056
DC braking / edge or level detec-
tion for [DB] input
01
01
A061
Frequency upper limit setting
0.0
0.0
A261
Frequency upper limit setting,
2nd motor
0.0
0.0
“A” Group Parameters
Default Setting
User
Setting
Func.
Code
Name
-FEF
(EU)
-FU
(USA)
Содержание SJ200 Series
Страница 53: ...SJ200 Inverter Inverter Mounting and Installation 2 15 Dimensional drawings continued SJ200 007HFEF 007HFU ...
Страница 185: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 207: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 254: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 265: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 269: ...SJ200 Inverter Appendix D D 5 L1 L2 L3 PE SJ200 inverter with book type filter M 3 ...