Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–40
Overload Advance Notice Signal
When the output current exceeds a preset
value, the [OL] terminal signal turns ON.
The parameter C041 sets the overload
threshold. The overload detection circuit
operates during powered motor opera-
tion and during regenerative braking. The
output circuits use open-collector
transistors, and are active low.
[OL]
Signal
1
0
ON
t
ON
Current
threshold
regeneration
power running
threshold
C041
C041
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
03
OL
Overload Advance
Notice Signal
ON
when output current is more than the set thresh-
old for the overload signal
OFF
when output current is less than the set threshold
for the overload signal
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
C041
Notes:
•
The default value is 100%. To change the level
from the default, set C041 (overload level).
•
The accuracy of this function is the same as the
function of the output current monitor on the [FM]
terminal (see
).
•
The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.
RY
+
–
12 11
L
H O OI
FM CM2
Example (requires output configuration—
see page
Inverter output
terminal circuit
OL
Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages
AL0
AL2
AL1
Inverter logic
circuit board
See I/O specs
on page
OL
Load
Power
supply
Содержание SJ200 Series
Страница 53: ...SJ200 Inverter Inverter Mounting and Installation 2 15 Dimensional drawings continued SJ200 007HFEF 007HFU ...
Страница 185: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 207: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 254: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 265: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 269: ...SJ200 Inverter Appendix D D 5 L1 L2 L3 PE SJ200 inverter with book type filter M 3 ...