Monitoring Trip Events, History, & Conditions
T
roub
leshooting
and Maintenance
6–6
NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values
are still correct. If the power is turned OFF while the [RS] (Reset) intelligent input
terminal is ON, an EEPROM error will occur when power is restored.
E 1 1
E 2 2
CPU error
A malfunction in the built-in CPU has occurred, so
the inverter trips and turns OFF its output to the
motor.
E 1 2
External trip
A signal on an intelligent input terminal configured as
EXT has occurred. The inverter trips and turns OFF
the output to the motor.
E 1 3
USP
When the Unattended Start Protection (USP) is
enabled, an error occurred when power is applied
while a Run signal is present. The inverter trips and
does not go into Run Mode until the error is cleared.
E 1 4
Ground fault
The inverter is protected by the detection of ground
faults between the inverter output and the motor upon
during powerup tests. This feature protects the
inverter, and does not protect humans.
E 1 5
Input over-voltage
The inverter tests for input over-voltage after the
inverter has been in Stop Mode for 100 seconds. If an
over-voltage condition exists, the inverter enters a
fault state. After the fault is cleared, the inverter can
enter Run Mode again.
E 2 1
Inverter thermal trip
When the inverter internal temperature is above the
threshold, the thermal sensor in the inverter module
detects the excessive temperature of the power
devices and trips, turning the inverter output OFF.
E 2 3
Gate array error
An internal inverter error has occurred in communica-
tions between the CPU and gate array IC.
E 3 5
Thermistor
When a thermistor is connected to terminals [6] and
[L] and the inverter has sensed the temperature is too
high, the inverter trips and turns OFF the output.
E 6 0
Communications error
The inverter’s watchdog timer for the communica-
tions network has timed out.
- - -
Under-voltage (brown-
out) with output shutoff
Due to low input voltage, the inverter turns its output
OFF and tries to restart. If it fails to restart, then the
alarm trips to record the under-voltage error event.
Error
Code
Name
Cause(s)
Содержание SJ200 Series
Страница 53: ...SJ200 Inverter Inverter Mounting and Installation 2 15 Dimensional drawings continued SJ200 007HFEF 007HFU ...
Страница 185: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 207: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 254: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 265: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 269: ...SJ200 Inverter Appendix D D 5 L1 L2 L3 PE SJ200 inverter with book type filter M 3 ...