SJ200 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–39
“B” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF
(EU)
–FU
(USA)
Units
B088 Restart mode after FRS
Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)
✘
00
00
—
RUN FRS ZST
B090 Dynamic braking usage
ratio
Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value
✘
0.0
0.0
%
BRD %ED 0000.0%
B091 Stop mode selection
Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)
✘
00
00
—
STP Slct DEC
B092 Cooling fan control
Selects when the fan is ON per
inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02... Fan is temperature-
controlled
✘
00
00
—
FAN-CTRL OFF
B095 Dynamic braking
control
Three option codes:
00... Disable
01... Enable during RUN only
02... Enable always
✘
00
00
—
BRD Slct OFF
B096 Dynamic braking
activation level
Range is:
330 to 380V (200V class),
660 to 760V (400V class)
✘
360/
720
360/
720
—
BRD LVL 00360V
B130 Over-voltage
LADSTOP enable
Pauses deceleration ramp when
DC bus voltage rises above
threshold level, in order to
avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable
✘
00
00
—
OVLADSTOP OFF
B140 Over-current trip
suppression
Two option codes:
00... Disable
01... Enable
✘
00
00
—
I-SUP Mode OFF
Содержание SJ200 Series
Страница 53: ...SJ200 Inverter Inverter Mounting and Installation 2 15 Dimensional drawings continued SJ200 007HFEF 007HFU ...
Страница 185: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 207: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 254: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 265: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 269: ...SJ200 Inverter Appendix D D 5 L1 L2 L3 PE SJ200 inverter with book type filter M 3 ...