![Hirschmann BATOne Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/hirschmann/batone/batone_user-manual_2138086031.webp)
2.6
Operating the device
WARNING
ELECTRIC SHOCK
Before connecting the electrical wires,
always
verify that the requirements
listed are complied with.
See Requirements for connecting electrical wires on page 7
.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
By connecting the supply voltage via a connector, you start the operation of
the device.
Proceed as follows:
Connect the power supply cable.
Enable the supply voltage.
2.7
Connecting data cables
Note the following general recommendations for data cable connections in
environments with high electrical interference levels:
Keep the length of the data cables as short as possible.
Use optical data cables for the data transmission between the buildings.
When using copper cables, provide a sufficient separation between the
power supply cables and the data cables. Ideally, install the cables in
separate cable channels.
Verify that power supply cables and data cables do not run parallel over
longer distances, and that ideally they are installed in separate cable
channels. If reducing the inductive coupling is necessary, verify that the
power supply cables and data cables cross at a 90° angle.
Use SF/UTP cables as per ISO/IEC 11801:2002.
Connect the data cables according to your requirements.
For more detail see
Ethernet ports on page 19
.
Installation BATOne
Release 01 01/2019
31