Wiring Instructions
75/86
netTAP NT 50 | Gateway Devices
DOC091202UM09EN | Revision 9 | English | 2013-02 | Released | Public
© Hilscher, 2010-2013
T-stubs does not exceed the maximum length listed in the following table.
There are two different types of cables. If both cables types are used within
the same network, the maximum length is:
Max. distance
Baud rate in
kBits/s
L
thick
+ 5 x L
thin
<= 500 m
at 125 kBaud
L
thick
+ 2,5 x L
thin
<= 250 m
at 250 kBaud
L
thick
+ L
thin
<= 100 m
at 500 kBaud
Table 74: DeviceNet Segment Length in dependence of the Baud rate
The DeviceNet cable contains the data line cables and the power supply
cables.