![hilscher netTAP NT 50 Series Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/hilscher/nettap-nt-50-series/nettap-nt-50-series_user-manual_2134827032.webp)
Device Drawings and Connections
32/86
netTAP NT 50 | Gateway Devices
DOC091202UM09EN | Revision 9 | English | 2013-02 | Released | Public
© Hilscher, 2010-2013
4.4
Schematic Diagram - Galvanic Isolation
The following schematic diagrams illustrate the internal connection between
the different connectors. This gives you the chance to properly install the
device in accordance with the potential equalization concept of your plant.
Note:
The PE connection (potential equalization) of the device is done via
the DIN rail.
4.4.1
Galvanic Isolation of NT 50-xx-EN Devices
The device types NT
50-CC-EN, NT
50-CO-EN, NT
50-DN-EN and
NT 50-DN-EN has three galvanically isolated areas. The coupling to PE is
shown in the following figure and in the following table.
Figure 5: Galvanic Isolation of NT 50-xx-EN Devices
Area
Con-
nection
Protocol
galv. Iso-
lation
Coupling
Coupling against PE
potential
Functional earthing to PE
HF
Cf = 10 nF / 500 V,
Lf = 47
μ
H
X1
-
no
Cx1
4 * 10 nF / 500 V
-
CC-Link inductive
Cx2
3,3 nF / 1000 V
directly to Combicon Pin 4
CANopen optically Cx2
1 M
Ω
// 15 nF / 1000 V
directly via the metal con-
nection of the D-Sub-male
connector
DeviceNet optically Cx2
1 M
Ω
// 15 nF / 1000 V
1 M
Ω
// 15 nF 1000 V
Combicon Pin 3
X2
Profibus DP
inductive
Cx2
1 M
Ω
// 2,2 nF/ 1000 V
directly via the metal con-
nection of the D-Sub female
connector
X3
Ethernet
inductive
Cx3
6 * 75
Ω
, 1 nF / 2000 V
Directly via the metal con-
nection of RJ 45 sockets
Table 30: Coupling NT 50-xx-EN Devices