Firmware recovery
50/75
Ø
Open the folder for your device and select the firmware file you want to
download to your device (firmware files can be recognized by the file
name extension .NXF).
Ø
Click
Open
.
Ê
The firmware file is being downloaded to the netHOST device. The old
firmware file is being overwritten. This can take a few seconds.
4. Check download.
Ø
In the right part of the
Explorer
window, right-click to open the context
menu, then choose
Refresh
.
Ø
Wait for a few seconds.
Ê
If the download has been successful, the downloaded firmware file is
displayed in
Port 0
:
Figure 11: Downloaded firmware in Explorer
Note:
If there is an IP address file (
NWID.NXD
) present in
Port_0
and
configuration files (
CONFIG.NXD
) in
Port_1
, and you do not want to
use these configuration files any longer, you can delete them in
order to completely reset the device to its “factory settings”. For this,
select the configuration file in the
Explorer
, then choose
Delete
command from the context menu.
5. Exit ComProX.
Ø
Close the
Explorer
window.
Ø
In the menu of ComProX, choose
Connection
>
Close
to close the
connection to the device.
Ø
Close
ComProX
.
6. Restart netHOST device.
Ø
Disconnect the voltage supply from the netHOST device, then
reconnect it.
ð
After restart, the SYS LED shows steady green light.
The state of the APL LED depends on whether a valid configuration is
still present in the device. If this is not the case, the APL LED is blinking
red.
netHOST NHST-T100 | LAN controlled master devices
DOC130401UM05EN | Revision 5 | English | 2018-05 | Released | Public