Technical data
150/166
IO-Link ports
Category
Parameter
Value
IO-Link Master (Class A)
Specification
V1.1.2
Port mode
IO-Link autoconfig
Min. cycle time
400 µs
Sensor supply
Output voltage
24 V DC, 1L-powered
Current
Maximum current consumption per IO-Link port without airflow: 400 mA.
Maximum current consumption per IO-Link port with airflow of ~ 0.5 m/s:
1800 mA.
Circuit
High-side driver, no back current protection from 1L+ output.
Table 40: Technical data IO-Link ports