10.1.13 AIFX-DN
AIFX-DN
Parameter
Value
Name AIFX-DN
Part No.
2800.510
Part
Description
DeviceNet assembly interface (with DeviceNet interface)
for the PC cards CIFX 104-DN\F, CIFX 104-DN-R\F
Interface
PC Card cifX
Connector
Cable Connector Fieldbus X1
(JST 10FMN-SMT-A-TF(LF)(SN), Pitch 1,0 mm)
Galvanic Isolation
isolated (optically isolated)
Isolation Voltage
1000 VDC (tested for 1 minute)
DeviceNet Interface
Connector
CombiCon male Connector, 5-polig
MNS
Module network status (duo LED)
Display
LED Display (on the reverse side
of the device)
The meaning of the MNS LED is depending on loaded
firmware. Refer to chapter
LED Descriptions
, page 64.
Power supply
Connector
Cable Connector Fieldbus X1
Operating temperature range*
-20 °C ... +70 °C
*Air flow during measurment
0,5m/s
Storage temperature range
-10 °C ... +70 °C
Humidity
10 … 95% relative humidity, no condensation permitted
Environmental
Conditions
Environment
For UL compliant usage:
The device must be used in a pollution degree 2
environment.
Dimensions (L x W x H)
23,7 x 31 x 18,5 mm (L = 23,7, without CombiCon male
Connector;
H
= width of the front panel)
Mounting/Installation
At the basic cards CIFX 104-FB\F, CIFX 104-FB-R\F:
Cable Connector Fieldbus X4 (X304)
Device
RoHS Yes
CE Sign
Yes
CE Sign
Emission, Immunity
Tested together with the corresponding basic card cifX..
UL Certification
The device is certified according
to UL 508
UL-File-Nr. E221530
Table 96: Technical Data AIFX-DN