Communication
95/154
Output process data
The following table gives a description of the process data structure of the
output process data and is valid for connection 5.
Byte
Number
of bytes
Output process data
Description
1
1 byte
DO status
Reserved
2
1 byte
Padding byte
Do not use
3 … 4
2 byte
DO data
Reserved
5
1 byte
WP01 Output enable
0: WP01 output data not valid.
1-255: WP01 output data valid.
6
1 byte
Padding byte
Do not use
7 … 22
16 byte
WP01 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP01. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.
23
1 byte
WP02 Output enable
0: WP02 output data not valid.
1-255: WP02 output data valid.
24
1 byte
Padding byte
Do not use
25 … 40
16 byte
WP02 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP02. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.
41
1 byte
WP03 Output enable
0: WP03 output data not valid.
1-255: WP03 output data valid.
41
1 byte
Padding byte
Do not use
43 … 58
16 byte
WP03 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP03. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.
59
1 byte
WP04 Output enable
0: WP04 output data not valid.
1-255: WP04 output data valid.
60
1 byte
Padding byte
Do not use
61 … 76
16 byte
WP04 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP04. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.
77
1 byte
WP05 Output enable
0: WP05 output data not valid.
1-255: WP05 output data valid.
78
1 byte
Padding byte
Do not use
79 … 94
16 byte
WP05 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP05. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.
94
1 byte
WP06 Output enable
0: WP06 output data not valid.
1-255: WP06 output data valid.
96
1 byte
Padding byte
Do not use
97 … 112
16 byte
WP06 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP06. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.
113
1 byte
WP07 Output enable
0: WP07 output data not valid.
1-255: WP07 output data valid.
114
1 byte
Padding byte
Do not use
115 … 130
16 byte
WP07 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP07. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.
131
1 byte
WP08 Output enable
0: WP08 output data not valid.
1-255: WP08 output data valid.
132
1 byte
Padding byte
Do not use
133 … 148
16 byte
WP08 process output data
IO-Link output data of the IO-Link Device wireless
connected to WP08. For a description of the data, see
manual of the manufacturer of the used IO-Link Device.