Configuration
55/154
Settings > Miscellaneous
Ø
Open the
Miscellaneous
sub tab.
Settings tab, Miscellaneous sub tab (example)
Parameter
Description
Value / Value range
Unique ID*
Unique ID of the IO-Link Device (9 Bytes)
Use the Unique ID (UUID) from the scan result.
0 … 0xFF, Default: 0
Slot type
Slot type of the found device
Use the slot type from the scan result.
Note: For a device featuring “Double slot” an even number must be
assigned as value for the slot.
Single slot, Double slot,
Default: Single slot
IMA Time 3 sec
(
calculated time
)
Requested I-Am-Alive time for the OPERATE mode
The I-Am-Alive time is calculated by multiplying the “time base”
with the “time multiplier”.
1.664 ... 10 min (for higher
values an error message
appears), Default: 3 sec
Time base: Used time base for the calculation of the I-Am-Alive
time.
1.664 ms, 5 ms, 1 sec, 1 min
Time multiplier: Used factor for the calculation of the I-Am-Alive
time.
1 … 255
Low power
device
Is the connected IO-Link Device a low power device or not
No, Yes, Default: No
Table 33: Settings in port configuration for IO-Link Device, Miscellaneous sub tab
* Values are in hexadecimal
Ø
To configure the Unique ID, use the Unique ID (UUID) from the scan
result.
Ø
If necessary, set the expected port parameters Slot type or Low power
device.
Ø
Configure the “IMA Time” (I-Am-Alive time).
NFD-3090-EIS-IOLM\W | Hardware, installation and commissioning
DOC200701UM02EN | Revision 2 | English | 2021-08 | Released | Public
© Hilscher 2020 - 2021