Commissioning
84/154
9.6
Wireless
For each track up to 8 IO-Link Devices can be connected via a wireless
connection.
The tracks and slots for the IO-Link Devices, configured with the wireless
IO-Link port configuration, must be unique! For each connected IO-Link
Device, 1 wireless track must be configured and 1 slot must be configured.
The presented commissioning example includes 1 connected IO-Link
Device. The chosen values were:
·
Track:
0x00
·
Slot:
0x00
Any further slots must be configured to free slots.
Note:
If slot type = “Double slot”, then the value for slot must be an even
number.
The following table shows an example for track and slot configuration for a
connected IO-Link Device if the slot type “Double slot” is configured.
Track
Slot 0
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7
0
W-device with double slot free
free
free
free
free
free
1
free
free
free
free
free
free
free
free
Table 51: Track and Slot – example 1 wireless device with slot type “double slot”
9.7
Setting date and time
The device has a built-in timing unit. To get the date and time from an NTP
server using Network Time Protocol (NTP), the device needs the IP
address of the NTP server. An OPC UA client is required to set the IP
address of the NTP server.
page 104] describes the nodes of the
OPC UA server for configuring the NTP client.
Setting date and time of the device via OPC UA
describes how to set the IP address of the NTP server via an OPC UA
client.