61
AdaptaPAK® Maintenance and Troubleshooting
8 - TROUBLESHOOTING - COMPRESSOR THERMAL PROTECTOR OPEN
SYMPTOMS
SYMPTOMS
POSSIBLE ACTIONS
Compressor
thermal protector
switch open
1. Operating beyond
design limits.
2. Discharge valve
partially shut
3. Blown valve plate and/
or gasket
4. Dirty condenser coil
5. Overcharged system
1. Add components
to bring conditions
within acceptable limits
(i.e., CPR/EPR valves,
additional condenser
surface, liquid injection,
etc.)
2. Open valve
3. Replace valve plate or
and/or gasket
4. Clean coil
5. Reduce charge
If, after performing the steps above, problems persist and you are not able to determine their cause, you may need
to contact Hillphoenix Field Service for assistance.