AdaptaPAK® Maintenance and Troubleshooting
1 - TROUBLESHOOTING - COMPRESSOR WILL NOT RUN
SYMPTOMS
SYMPTOMS
POSSIBLE ACTIONS
Compressor will
not run
1. Main switch open
2. Blown Fuses
3. Thermal overloads
tripped
4. Defective contactor or
coil
5. System shut down by
safety devices
6. No cooling required
7. Liquid line solenoid will
not open
8. Motor electrical trouble
1. Close switch
2. Check electrical
circuits and motor
winding for shorts or
grounds
Investigate for possible
overloading
Replace fuses after fault
has been corrected
3. Overloads are
automatically reset
Check unit closely when
it comes back online
4. Repair or replace
defective component
5. Determine type and
cause of shutdown and
correct it before resetting
safety switch
6. None; wait until
system calls for cooling
7. Repair or replace coil
8. Check motor for open
windings, short circuit, or
burnout