multiMAX™ Controller for AdaptaPAK®
Hillphoenix® multiMAX™ Controller (showing input and output connections)
Definitions of Inputs and Outputs corresponding to the multiMAX™ Controller I/O.
J12 and J13 - Compressor Enable, Normally Open Relays
J12: Compressors 1, 2, 3 and J13: Compressors 4, 5, 6
Compressor Enable = a Normally Open (NO) relay that is used by the controller to energize one or more compressors
in a given suction group. Energizing or de-energizing compressors is done in order to maintain the proper saturated
suction pressure for the rack.
J14 - Split Condenser Control, Normally Open Relay
J14: Split Condenser Valve
If split condenser operation is called for, the relay will close and only one portion of the condenser will receive
refrigerant flow.
J16 - Condenser Fan Control, Normally Open Relay
J16: Condenser Fans 1, 2, 3
As required to meet system operational demands, condenser fans will be turned on or off. (Cycled to maintain drop
leg pressure.)
J17 - Optional, Water Heat Reclaim, Normally Open Relay
J17: Water Heat Reclaim Valve
With this option, controller would close the relay and thus opening a valve to heat water in a heat exchanger.