![Hillphoenix Adaptapak ADP-M0000-L0032 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/hillphoenix/adaptapak-adp-m0000-l0032/adaptapak-adp-m0000-l0032_installation-and-operation-manual_2134298006.webp)
6
AdaptaPAK® Parallel Refrigeration System
Whether a 2 fan unit or a 3 fan unit, the AdaptaPAK® system will arrive fully designed for your load configuration,
and ready for placement at the site in your designated pad or roof location. Placement would most commonly be
performed with a cable/rope with proper rigging (refer to drawings for details).The remaining tasks would include
charging with refrigerant, making electrical connections, and completing the connection of the AdaptaPAK® unit up
to your refrigeration loads.
Dimensions of AdaptaPAK® Units
The 2 fan unit is 139 1/4 inches long by 50 1/2 inches wide by 51 1/4 inches high.
The 3 fan unit is 180 inches long by 50 1/2 inches wide by 51 1/4 inches high.
The 4 fan unit is 220 inches long by 50 1/2 inches wide by 51 1/4 inches high.
Clearances for AdaptaPAK® Units (2 fan and 3 fan)
Air Intake: 36 inches recommended
Air Exhaust: 36 inches recommended
Piping Clearance: 36 inches (minimum) recommended
Hinged Front Door: 36 inches (outward from door) by 50 inches (width)
NEC Electrical: 36 inches (outward from door) by 50 inches (width)
Weights of AdaptaPAK® Units (2 fan and 3 fan)
Fans
Compressors
Estimated Weight
2
4
3,000 lbs
3
6
3, 500 lbs
4
8
4,000 lbs
AdaptaPAK® Units’ Standard Features
The following features are provided as standard equipment on AdaptaPAK® units (2 fan, 3 fan, and 4 fan):
• Pre-painted, galvanized steel cabinet (pueblo tan).
• Refrigerants available are R-407A and R-448A/R-449A
• Uncoated copper tube/aluminum fin condenser coil.
• Main power is 208V.
• Scroll compressors (only).
• Digital scroll compressor as the lead compressor per suction group
• Receiver includes analog liquid level indicator/alarm.
• Replaceable core filter/drier and sight glass.
• Oversized receiver.
• Fixed speed AC condenser fan motors.
Содержание Adaptapak ADP-M0000-L0032