Chapter 6. Parameter Setting
6-18
Menu
Menu name
Unit
Display range
Initial value
Mode
P2-23
Autotune Range
0 ~ 9
0
SP
Prior to using the automatic setting function, input approximate ratio of system inertia to motor
System inertia (Motor i load inertia)
Inertia
Motor inertia
to define the range.
If the ratio of system inertia to motor inertia is unknown, input "0".
Ration of system inertia to
motor inertia (multiples)
Input value
1 ~ 500
0
2 ~ 3
1
2 ~ 10
2
3 ~ 15
3
10 ~ 25
4
15 ~ 100
5
25 ~ 200
6
100 ~ 300
7
200 ~ 400
8
300 ~ 500
9
Menu
Menu name
Unit
Display range
Initial value
Mode
P2-24 Autotune
ON/OFF
ON/OFF
OFF
SP
ON: Auto set function is activated and the results are automatically stored in [SC LOOP
Gain (P2-03)], [Inertia Ratio (P2-22)].
Menu
Menu name
Unit
Display range
Initial value
Mode
*P2-25 Parameter
Init
Currt/dFLT
currt
SPT
When servo is used, parameters are set in various values. To restore parameters to servo's
initial value (basic set value) during operation, press Prog key. When "Parameter dFlt" is
displayed on the screen, press Enter key. All parameters except the motor parameters ([P1-
01] - [P1-09]) are restored to their initial values.
Menu
Menu name
Unit
Display range
Initial value
Mode
P2-26 SPDIN
Delay ms
0~100
0
S
Sets the analog speed command (SPDIN) delay in terms of [ms].
Recommended set value range: 0 – SCI TC (P2-04)/20
(Example) If SCI TC (PP2-04) is 50 (ms], the set range is 0 - 2.5[ms].