Chapter 10. How to Use Speed/Position Servo
2
10-
10.2.1 Input contact signal function and use table
Name
Pin No.
Function and Use
SVONEN 18
ON: Servo start command
OFF: Servo start command reset
DIR 16
Selects servo rotation direction[Valid only in speed control mode]
(Off: Command direction rotation, ON: Counter-command direction rotation)
STOP/
START
13
Forcibly zeros (stops) the speed command value, or starts operation.
(Can be selected from parameter P2-29)
CCWLIM 15
OFF: Motor CCW running limited
ON: Motor CCW running allowed
CWLIM 40
OFF: Motor CW running limited
ON: Motor CW running allowed
ESTOP 39
Forcibly ignores all input status of the servo drivers in case of external
emergency, and shuts off (free-run) motor operation after rapidly
decelerating the motor.
(Contact type can be selected from parameter P2-30)
ALMRST
CLR
38
Resets alarm status if turned ON(Control speed)
At ON, reset alarm and clear error pulse between command pulse and
current position. (Control torque)
PI/P 41
Selects speed control mode (Turned OFF during normal operation)
ON: Proportional control, OFF: Proportional integration control
TLIM
14
ON: Analog torque limit; Off: Digital torque limit.
SPD1
SPD2
Selects rotation speed command by combination of the two signals
(Speed control mode).
GEAR1
GEAR2
43
17
Slects electronic gear by conbination of the two signals.(Position control
mode)
TPE 42
ON: Operates as speed servo.
OFF: Operates as position servo.
Where ON: Applicable contact is connected to "GND24".
OFF: Applicable contact is connected to "+24V", or applicable contact not connected.
10.2.2 Output contact signal function and use table
Name
Pin No.
Function and Use
RDY 21
ON: Main power and auxiliary power are connected to servo without any
alarm.
INSPD
ON: Motor speed reached designated level(Control speed)
INPOS
22
Reached designated pulse position (Position control)
ZSPD
47
ON: Motor speed is zero.
BRAKE 48
Output signal for external machine brake drive
ON: Brake reset, OFF: Brake drive
ALARM
20
ON: Normal status, OFF: Alarm detected
A_CODE0
A_CODE1
A_CODE2
45
19
44
Displays alarm type.
See the table below [Alarm Code output status].
TRQOUT
46
ON: Servo is under torque limit.
Where ON: Applicable contact is connected to "GND24".
OFF: Applicable contact is connected to "+24V", or applicable contact not connected.