Chapter 6. Parameter Setting
6-14
Menu
Menu name
Unit
Display range
Initial value
Mode
P2-03
SC LOOP Gain
rad/sec
0 ~ 5000
By capacity
SPT
(Description continued)
If the ratio of the overall system inertia (Sum of motor inertia and load inertia) to the motor
inertia is set in [Inertia Ratio (P2-22)], or if the value set by using the autotuning [Autotuning
(P2-24)] provided with the servo is the same as the following, the recommended set values
of [SC Loop Gain (P2-03)] by servo capacity are as follows.
[Table]
Servo driver capacity
FDA5001~04
FDA5005~5075
Inertia Ratio (P2-22) set
value
Recommended SC Loop
Gain (P2-03) set value
Recommended SC Loop
Gain (P2-03) set value
1.0
500 ~ 1000
100 ~ 200
2.0
350 ~ 500
70 ~ 200
3.0
300 ~ 500
50 ~ 150
5.0
200 ~ 300
40 ~ 100
10.0
150 ~ 250
30 ~ 80
20.0
100 ~ 150
20 ~ 60
30.0
60 ~ 100
-
(Caution !!)
However, the recommended SC Loop Gain (P2-03) set values may be deviated
according to the status of the load.
If the
□
80 or
□
130 motor is controlled by servo FDA-5004, use SC Loop Gain
(P2-03) of FDA-5005.
Menu
Menu name
Unit
Display range
Initial value
Mode
P2-04
SC I TC [ms]
ms
1 ~ 10000
20
SPT
Reducing the speed integrating time constant can improve the transient response
characteristics of speed control and normal status characteristics. However, if the time
constant is reduced excessively, overshoot may occur. Select appropriate value. If 10,000 is
input, the speed integrating time constant is considered indefinite, and the speed control
turns to P control form.
Recommended set value
=
10000
[SC LOOP Gain (P2 - 03)]
[ms]
Recommended minimum set value
=
3000
[SC LOOP Gain (P2 - 03)]
[ms]