Term
Description
(
Settings
Must temperature
The boiler is charged to the set temperature within the charging
time.
For heat pumps the boiler temperature should not be set higher
than 55°C!
Min. loading / temperature
Activate/setting the min. loading / temperature (ON/OFF)
If the hot water tank min. loading / temperature is activated out
of loading time, the hot water tank temperature will be load up to
the set min. loading /
If within the loading times the hot water tank temperature is
lower than the min. loading / temperature value, the hot water
tank is loading up to the must temperature.
Temp. increase
Setting up the temperature increase of the required
Because of heat losses a surcharge to the hot water tank must
temperature can be set.
Max. Loading time
Setting up maximum hot water tank loading time, when hot water
tank is loaded to hot water tank set temperature
If the hot water tank is
an error appears and the hot water tank doesn't continue
loading.
Legio temperature
Setting up the legionella temperature:
Every 10 days the hot water tank is heated up within the set
loading times to the
A deactivation of this parameter is done by setting up the
legionella temperature to 0 °C.
For heat pumps the legionella protection funtion should be
implemented with a further heat generator!
Circulation pump /
circulation temperature
Activates the circulation pump (ON/OFF) respectively setting of
the circulation temperature
The control of the circulation pump is done via the circulation
times.
When activating the circulation pump the parameter circulation
pump
circulation pump can be controlled manually.
A deactivation of this parameter is done by setting up the
legionella temperature to 0 °C.
Loading valve
By activating the loading valve the hot wat
heat pump and not via the buffer.
Time program
Time 1
By pressing this field, between three times can be selected.
time 1: 05:00
time 2 :17:00
time 3: 00:00
05:00 – 07:30
Setting up
weekday.
Monday preset gets assigned to remaining weekdays.
T-CONTROL - Hot water tank module
Description
only visible, if circulation pump is activated)
The boiler is charged to the set temperature within the charging
For heat pumps the boiler temperature should not be set higher
than 55°C!
Activate/setting the min. loading / temperature (ON/OFF)
If the hot water tank min. loading / temperature is activated out
of loading time, the hot water tank temperature will be load up to
the set min. loading / temperature.
If within the loading times the hot water tank temperature is
lower than the min. loading / temperature value, the hot water
tank is loading up to the must temperature.
Setting up the temperature increase of the required temperature
Because of heat losses a surcharge to the hot water tank must
temperature can be set.
Setting up maximum hot water tank loading time, when hot water
tank is loaded to hot water tank set temperature
If the hot water tank isn't charged up within the set loading time
an error appears and the hot water tank doesn't continue
loading.
Setting up the legionella temperature:
Every 10 days the hot water tank is heated up within the set
loading times to the legionella temperature to kill bacteria.
A deactivation of this parameter is done by setting up the
legionella temperature to 0 °C.
For heat pumps the legionella protection funtion should be
implemented with a further heat generator!
Activates the circulation pump (ON/OFF) respectively setting of
the circulation temperature
The control of the circulation pump is done via the circulation
times.
When activating the circulation pump the parameter circulation
pump change to circulation temperature or rather in agg
circulation pump can be controlled manually.
A deactivation of this parameter is done by setting up the
legionella temperature to 0 °C.
By activating the loading valve the hot water tank is loaded via the
heat pump and not via the buffer.
By pressing this field, between three times can be selected.
time 1: 05:00 – 07:30
time 2 :17:00 – 21:00
time 3: 00:00 – 00:00
Setting up individual hot water tank loading times of every
weekday.
Monday preset gets assigned to remaining weekdays.
tank module
7
35
Unit
The boiler is charged to the set temperature within the charging
For heat pumps the boiler temperature should not be set higher
°C
Activate/setting the min. loading / temperature (ON/OFF)
If the hot water tank min. loading / temperature is activated out
of loading time, the hot water tank temperature will be load up to
If within the loading times the hot water tank temperature is
lower than the min. loading / temperature value, the hot water
°C
temperature
Because of heat losses a surcharge to the hot water tank must
°C
Setting up maximum hot water tank loading time, when hot water
n't charged up within the set loading time
an error appears and the hot water tank doesn't continue
h
Every 10 days the hot water tank is heated up within the set
legionella temperature to kill bacteria.
A deactivation of this parameter is done by setting up the
For heat pumps the legionella protection funtion should be
°C
Activates the circulation pump (ON/OFF) respectively setting of
The control of the circulation pump is done via the circulation
When activating the circulation pump the parameter circulation
change to circulation temperature or rather in agg-test the
A deactivation of this parameter is done by setting up the
-
er tank is loaded via the
-
By pressing this field, between three times can be selected.
-
individual hot water tank loading times of every
-
-