8
STEP 4 S – Select the time for the second cycle (which in this example is RINSE) using
or
button. Press NEXT to go to Step 5S. Press REGEN to return to the previous step.
STEP 5 S – Set Gallons Capacity using
or
button. If value is set to:
• “oFF” regeneration will be based solely on the day override set (see Installer Display/Settings
Step 3, page 6 or
• as a number of gallons (allowable range 20 to 250,000) regeneration will be based on the
value specified.
Increment increase is 20 for the range 20 to 2000, 100 for the range of 2000 to 10,000 and
500 for the range of 10,000 to 50,000 and 2000 for range of 50,000 to 1,500,000.
Press NEXT to go to Step 6S. Press REGEN to return to previous step.
STEP 6 S – Set Regeneration Time Options using the
or
button. If value is set to:
• “DELAYED” means regeneration will occur at the preset time;
• “IMMEDIATE” means regeneration will occur immediately when the gallons capacity
reaches 0 (zero); or
• “D IMMEDIATE” means regeneration will occur at one of the following:
- the preset time when the gallons capacity falls below the reserve or the specified number of
days between regenerations is reached, whichever comes first; or
- immediately after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
See page 26 for more options. Factory Setting is Delayed. Press NEXT to go to Step 7S.
Press REGEN to return to previous step.
STEP 7 S – Set Relay to activate by Time, Gallons, Regen Gallons, Lockout, Off or Ser-
vice Alarm by using
or
buttons. A relay can be used to operate a chemical feed pump
or solenoid, etc. The choices are:
•
Relay Triggered on Time - Relay activates after set number of minutes after start of regen-
eration. Start of regeneration is defined by first backwash cycle, dn brine or up brine,
whichever is first. Relay deactivates after set time. Press NEXT for programming.
• Relay Triggered on Gallons - Relay activates every set number of gallons while in service
and deactivates after set time. Press NEXT to go to 11S for programming.
• Relay Triggered on Regen Gallons - Relay activates after set number of gallons in service
or gallons used during regeneration and de-activates after set time or when meter stops
registering flow, whichever comes first. Press NEXT to go to 14S for programming.
• Service Alarm - Relay activates on service alarm setting: gallons, time or both, see step 16S.
• Relay Triggered for Lockout - The relay closes at set time before or after the start of
regeneration, as referenced by start of backwash. Negative start time delays regenera-
tion by that amount. Selection of energizing relay for complete regeneration cycle plus 2
minutes before and after is available by selecting REGEN for time setting, see step 17S.
• Off - If off is selected, Steps 7S to 19S will not be shown. Factory setting = OFF.
Press NEXT to go to step 20S or other selection screens for relay settings.
STEP 4S
SET
6:00
MIN
➔
STEP 5S
SET
OFF
GALLONS CAPACITY
➔
RINSE TIME
STEP 7S
RELAY 1 "TIME"
TRIGGER
➔
SET
STEP8S
RELAY 1 SET POINT
10
➔
MIN
RELAY 1 DURATION
3:00
MIN
➔
STEP 9S
SET
SET
RELAY 1 "GALLONS"
➔
TRIGGER
SET
STEP 10S
STEP 6S
SET
DELAYED
➔
REGEN
STEP 8 S –
If off was selected in previous step, this screen does not appear.
If Time chosen to Activate Relay, use up and down arrows to set # of minutes
AFTER START OF REGEN to activate relay. Start of regeneration is defined as
first Backwash or Regenerant Draw mode. Time Range = 1 – 500 minutes. Press
NEXT to go to Step 9S.
STEP 9 S –
Use Up and Down arrows to set duration of relay activation in minutes.
Time Range is 0:01 (1 second) to 500:00 (500 minutes) Press NEXT to go to Step
20S. Press REGEN to return to previous step.
STEP 10 S –
Gallons chosen to activate relay. If Off or Time was selected in previous
steps, this screen does not appear. Press NEXT for trigger programming.