FILTER SETUP

Manual Regeneration

Sometimes there is a need to regenerate the system, sooner than when the system calls for it, 

usually referred to as manual regeneration.  There may be a period of heavy water usage because 

of guests or a heavy laundry day.

To initiate a manual regeneration at the preset delayed regeneration time, press and release 

“REGEN”.  The words “REGEN TODAY” will flash in left corner of display to indicate that the 

system will regenerate at the preset delayed regeneration time.  If you pressed the “REGEN” 

button in error, pressing the button again will cancel the request. 

To initiate a manual regeneration immediately, press and hold the “REGEN” button for three 

seconds.  The system will begin to regenerate immediately.  The request cannot be cancelled.  You 

must cycle all the way through the cycles to make it stop.  PLEASE NOTE:  This will reset the meter.

Regeneration Mode

Typically a system is set to regenerate at a time of low water usage.  An example of a time with low 

water usage is when the household is asleep.  If there is a demand for water when the system is 

regenerating, untreated water will be supplied.

When the system begins to regenerate, the display will change to include information about the step 

of the regeneration process and the time remaining for that step to be completed.  The system runs 

through the steps automatically and will reset itself to provide treated water when the regeneration 

has been completed.

Figure 11

STEP 1S

STEP 2S

FILTERING

STEP 3S

SET   

12:00

MIN

STEP 1S – Press NEXT and 

 simultaneously for 3 seconds.  If screen in Step 2S does 

not appear in 5 seconds the lock on the valve is activated.  

STEP 2S –  Select between softening or filtering.  A flashing "SOFTENING" or 

"FILTERING" will appear.  Choose FILTERING using 

 

or 

 

button.   Factory setting is 

Filtering.  Press NEXT to go to Step 3S.  Press REGEN to exit Filter System Setup.

STEP 3S – Select the time for the first cycle (which in this example is BACKWASH) using 

the 

 

or 

 

button.  Press NEXT to go to Step 4S.  Press REGEN to return to previous step.

3

"REGEN TODAY" DAYS TO A REGEN

Regeneration Step

(shows time remaining in regen step 

is 8 minutes, 22 seconds)

REGEN

8:22

BACKWASH

         = 

 Up Arrow              = 

 Down Arrow

  Tank Diameter 

10” 

12” 

13” 

14” 

16” 

18”

  Square Ft Area 

0.545 

0.785 

0.921 

1.07 

1.38 

1.76

  Back wash Rate GPM 

10 

12 

15 

20

Backwash rates illustrated above are based upon 8-12 GPM per square foot of area and water with a temperature of 50º F. These 

flow rates are typical for use with medias such as Carbon; Multi-Media, Neutralizing Media, or Birm. Specific media and conditions 

may require specific flow rates.

GENERAL FILTER BACKWASH FLOW RATES

8" Through 13" Diameter Tanks
        

Regeneration Cycle       Minutes

1st Cycle           Backwash   

          12

2nd Cycle          Rapid Rinse             6

14" and Larger Diameter Tanks
        

Regeneration Cycle       Minutes

1st Cycle           Backwash   

          20

2nd Cycle          Rapid Rinse            10

All filters factory set to backwash every 3 days except neutralizing filters are set to backwash every 2 days.

Factory Settings:

SET

BACKWASH TIME

TYPE

Содержание ProMate-6.0

Страница 1: ...Owner s Filter Manual Manufactured by HELLENBRAND INC 404 Moravian Valley Road Waunakee Wisconsin 53597 www hellenbrand com info hellenbrand com FILTER SYSTEM 107207 Rev B 5 8 18 2007 2018...

Страница 2: ...assistance for servicing your water filter please contact the dealer who installed this system Job Specification Sheet 2 Pre Installation Check List 3 Installation Instructions 4 Programming 5 Initia...

Страница 3: ...recommended with all electric controls Existing Plumbing Condition of existing plumbing must be free from lime and iron build up Piping that is built up heavily with lime and or iron must be replaced...

Страница 4: ...joints should be cool and solvent cements should be set before installing the nut split ring and o ring Avoid getting primer and solvent cement on any part of the o rings split rings bypass valve or...

Страница 5: ...cally When water is being treated i e water is flowing through the system the word GPM flashes on left side of display when other than flow rate is displayed Figure 8 DAYS TO A REGEN 6 CAPACITY REMAIN...

Страница 6: ...to prevent multiple units from regenerating at the same time Step 5I Regeneration Time minutes Set the minutes of day for regeneration using or buttons This display will not be shown if system is set...

Страница 7: ...vide treated water when the regeneration has been completed Figure 11 STEP 1S STEP 2S FILTERING STEP 3S SET 12 00MIN STEP 1S Press NEXT and simultaneously for 3 seconds If screen in Step 2S does not a...

Страница 8: ...tivates after set time Press NEXT for programming Relay Triggered on Gallons Relay activates every set number of gallons while in service and deactivates after set time Press NEXT to go to 11S for pro...

Страница 9: ...arrows to set duration of relay activation in minutes Range 0 01 1 second 500 00 500 minutes Press NEXT to go to Step 20S Press REGEN to return to previous step STEP 13S If REGEN gallons chosen to act...

Страница 10: ...his display will show dashes if a water meter is not installed Press the NEXT button at any time to go to Step 6 D Press REGEN to return to the previous step DIAGNOSTICS STEP 1D STEP 2D 2 DAYS SINCE R...

Страница 11: ...on at time of stall Press NEXT to exit valve history STEP 1VH VALVE HISTORY STEP 2VH 970 TOTAL DAYS STEP 3VH 235 STEP 4VH 175 GAL x1K RETURN TO NORMAL MODE Can not be reset TOTAL REGENS TOTAL GALLONS...

Страница 12: ...No Hard Water Bypass During Regeneration See instructions in Step 6CS Reclaim Enabled Allows control to operate in Reclamation Mode up to 3 reclaim events can be programmed See instructions in Step 8C...

Страница 13: ...ating MAV will transition back to Service after the completion of the preset duration time labeled Reclaim Duration Three reclaim events are possible Select either Reclaim Enabled Reclaimed 2x for two...

Страница 14: ...to return to previous step Only displays if RECLAIM 2X is selected Use the or buttons to select number of minutes after start of regeneration for Aux MAV to divert waste water Press NEXT to program n...

Страница 15: ...or buttons until selection of fourth cycle appears in left upper corner in this example RINSE is selected Press NEXT to go to Step 18CS Press REGEN to return to previous step STEP 18CS Press the or bu...

Страница 16: ...osen drive cap gear 1 4 turn timed out trying to reach next position C2 Address high drive forces C3 Motor failure during regeneration replace motor Error Code 104 Motor ran too long D1 Piston unable...

Страница 17: ...ce battery if less than 3 volts F Defective PC board F Replace PC board 3 Control does not display correctly A Power outage 2 years A Reset time of day replace lithium coin type battery time of day on...

Страница 18: ...r assembly C Defective relay See figure below C Replace Relay D Defective PC Board D Replace PC Board E Faulty wire connections between E Check and repair wire connections PC board and relay 7 Relay e...

Страница 19: ...6 21 x 62 1 110569 5 Filter Media Contact dealer for filter media type quantity 6 Underbedding Contact dealer for underbedding type quantity Vortech tank does not use underbedding Owners Manual 1 1072...

Страница 20: ...OVER AND DRIVE ASSEMBLY After completing any valve maintenance involving the drive assembly or the drive cap assembly and pistons press and hold NEXT and REGEN buttons for 3 seconds or unplug power so...

Страница 21: ...The nuts and caps are designed to be unscrewed or tightened by hand or with the special plastic wrench If necessary a pliers can be used to unscrew the nut or cap Do not use a pipe wrench to tighten o...

Страница 22: ...on threads Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connection Teflon tape is not necessary on the nut connection nor caps because of o rings...

Страница 23: ...ss Handle 2 7 109479 Bypass Rotor Seal Retainer 2 8 102159 O Ring 135 2 9 102161 O Ring 112 2 10 102160 O Ring 214 2 Bypass Valve Not Shown Bypass Vertical Adapter Assembly ORDER NO DESCRIPTION QTY 10...

Страница 24: ...ants on threads Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connection Teflon tape is not necessary on the nut connection nor caps because of o ri...

Страница 25: ...ble the valve the wrench shown in various positions on the valve may be purchased to aid in assembly or disassembly Wrench part number is 102892 Loosens Drain Nut in Polytube Applications Loosens Driv...

Страница 26: ...minutes of no water usage when gallon capacity reaches 0 1 to 28 1 to 28 1 to 28 20 to 250 000 20 to 250 000 20 to 250 000 20 to 250 000 Reserve Gallons Regeneration Type Days Override Results Reserv...

Страница 27: ...27 NOTES...

Страница 28: ...s paragraph sets forth the exclusive remedy for any valid warranty claims against Hellenbrand THIS WARRANTY DOES NOT COVER defects caused by sand sediment or bacteria fouling accident fire flood Act o...

Отзывы: