15
STEP 15CS – This display will be available to select the use of an outside signal to control the
initiation of a regeneration. Selection only matters if a connection is made to the two pin connec-
tor labeled DP SWITCH located on the printed circuit board. Following is an explanation of the
options:
• ON 0 REGEN – If the dP switch is closed for an accumulative time of 2 minutes, a regenera-
tion will occur immediately.
• DELAY REGEN – If the dP switch is closed for an accumulative time of 2 minutes, a regenera-
tion will occur at the schedule regeneration time.
• HOLD REGEN – If the dP switch is closed a regeneration will be prevented from occurring.
• OFF - Factory setting is off
Press NEXT to go to Step 16CS. Press REGEN to return to previous step.
STEP 16CS – Press the
or
buttons until selection of first cycle appears in left upper cor-
ner, in this example BACKWASH is selected. Press NEXT to go to Step 17CS. Press REGEN
to return to previous step.
STEP 17CS – Press the
or
buttons until selection of fourth cycle appears in left upper
corner, in this example RINSE is selected. Press NEXT to go to Step 18CS. Press REGEN to
return to previous step.
STEP 18CS – Press the
or
button until last regeneration cycle; END appears (up to 9
regeneration modes are possible). End must be selected as last cycle. Press NEXT to go to
Step 19CS.
STEP 19CS – Press the
or
button to select number of standard regenerations which
would trigger one alternate regenerant fill amount. Brine elbow must be installed for this to
function. Range: 1-99. Factory setting is OFF. Press NEXT to go to Step 20CS.
STEP 20CS – Select amount of regenerant to be used when alternate regeneration requested.
Brine elbow usually contains 0.5 gpm flow control button. This screen is not displayed if off is
selected in previous step. Softener Range 0.1-200 lbs. Software assumes 0.5 gpm flow control
is in place to determine length of fill time. Filter Range 0.05-20.0 Gallons.
CYCLE 1
BACKWASH
SET
CYCLE 4
RINSE
SET
CYCLE 6
END
SET
STEP 16CS
STEP 17CS
STEP 18CS
ON 0
AUXILIARY INPUT
SET
REG
STEP 15CS
➔
➔
➔
➔
REGENS
ALT FILL TRIGGER
SET
STEP 19CS
➔
OFF
15.0
ALT FILL AMOUNT
SET
STEP 20CS
➔
LBS
Содержание ProMate-6.0
Страница 27: ...27 NOTES...