Cut-Out devices
7.1
Standard FAA connector type
The Cut-out device includes the following parts:
-
The Aluminum device with four nos. female FAA high Voltage connectors.
Two of the plugs are connected to each end of the output transformer (S1 and S2 on
terminals –XX4), and two are connected to ground.
-
Two nos. flexible high voltage cable, length app. 0,8 m, with vulcanized FAA high voltage
male connector in one end. The other end is connected to the series circuit on the lightning
arrestors.
Function:
In normal operation are the two male plugs mounted in the upper female FAA connectors, and in
this way connected to the output transformer. For service, or during work on the series circuit, the
two male plugs are mounted in the grounded female plugs.
Now the CCR is disconnected from the series circuit, and the series circuit is grounded.
Cables and plugs are designed for 20A and max 5KV.
IMPORTANT:
The plugs are only to be moved with the CCR key switch in position OFF (=AUS).