CCR961 MANUAL-GB
23
Version B2:01-07-2015
The CCR is entered into
Factory Mode
:
>E<
Enter code for Factory Mode
With >
< (arrow right) the menus are controlled/corrected as follows:
Menu
Nr.
Menu
Name
Default
Value
Settings for circuits
with Uout-max
< 1500V
Settings
for other
circuits
Comments
F1 Ucurve-zero 160 Default,
except for CCR’s on
230V supply, where
a value of 100 is
selected
In circuits with harmonics, instability
in LAME or in the value for
regulation reserve can occur. In such
cases the value is increased in steps of
20.
F2
Iout
This calibration is done in the factory
F3
Hour count
Hour counter for 100 % step can be
reset by pressing >0<
F4
Imin delay
0,5s
Default
Default
Delay by Normal Imin switch-off
(I < 1,5A)
F6 On-ref
Band 0,4A Default
Default
F7 Imax
calibrate
6,75A Default
Default
F8 On-ref
out
delay
4,0s Default
Default
Delay towards Remote Control
F9 I-peaktime 0,4 Default
Default Ipeak regulation during Soft Start
F10
I-peakmax
10,0Ap Default
Default
Ipeak value during Soft Start
F11 I
peak-limit 4100
(OFF)
4100
(Off)
4000 Max.
Value
4100
F12 Z
engage
delay
0,6s
Default
Default
Z delay during switch-on.
Note: F14 must be adjusted first.
F13
Z alarm delay
0,5s
Default
Default
Z delay in normal use
F14 Z
Factor
2,0
4,0
2,5
F15
User Password 0725
Default
Default
Password for User Mode can be
changed
F16
Reg. max
35
Default
Default
Reg. “max”:
Max “pyks’s” in each regulation step
F17 Up
regulation 0,4
Default
Default Factor for calculated reg. step, up
F18
down regulation 0,6
Default
Default
Factor for calculated reg. step, down
F19
Reg. delay
3
Default
Default
Factor (x10mS) delay between
regulations
F20
LED init value
250
Default
Default
Pyk-Limit during softstart
F21
Thy. max range 80
Lowest TG. angle
F22
Imin-M Off
Inactive Default
Default
Imin-M deactivated (only possible in
Local operation mode
F23 Imin-N
Off Inactive
Default Default
Imin-N
deactivated (only possible in
Local operation mode
F24
ISO type
1
1: Analog (in ranges)
2: Digital, direct value in K
Ω
F25
Inorm type
1
100% output current:
0: 2,2A
1: 6,6A
2: 13,2A
F19
Store Data
Store new values by pressing >E<
Содержание CCR 961-SW4.00
Страница 1: ...Regulator type CCR 961 SW4 00 USER MANUAL GB...
Страница 9: ...CCR961 MANUAL GB 9 Version B2 01 07 2015...
Страница 13: ...CCR961 MANUAL GB 13 Version B2 01 07 2015...
Страница 19: ...CCR961 MANUAL GB 19 Version B2 01 07 2015 CCR front view...
Страница 36: ...CCR961 MANUAL GB 36 Version B2 01 07 2015...