CCR961 MANUAL-GB
32
Version B2:01-07-2015
Adjustments:
Minimal procedure
1.
The Key switch is set in position Manual
2.
>E<
3.
Enter code for user menu
4.
>E<
5.
Press >5< to start of learn procedure
6.
Confirm ”All lamps OK?” by pressing >E<
7.
The CCR will automatically run through all active steps
8.
When the question ”-1 lamp?” pops up, press >C< shortly to end the Learn procedure
9.
Then press >
→
< for some sec. until the ”Store Data menu“ is shown
10.
Store the learned data by pressing >E<
11.
”Minimal procedure” for LAME is finalized
If only the Minimal procedure is performed, the CCR will not be able to ”recognize” the circuit
with faulty lamps. It is therefore necessary to let the CCR use data from a ”standard transformer”.
In User menu, U2 can be adjusted a desired L (delta) value. This procedure is useful to secure
normal operation, without LAME alarms, but the accuracy is low.
Normal procedure
1.
The Key switch is set in position Manual
2.
>E<
3.
Enter code for User Menu
4.
>E<
5.
Press >5< to start the learn procedure
6.
Confirm ”All lamps OK?” by pressing >E<
7.
The CCR will automatically run through all active steps
8.
When the question ”-1 lamp?” pops up, remove one lamp in the circuit and press >E<
9.
When the question ”-2 lamp?” pops up, press >C< shortly
10.
Press >8< for ”Break-point”
11.
Upon request for Break-point , enter 3
12.
When the question ”-3 lamps?” pops up, remove 2 more lamps from isolating transformers
in the circuit and press >E<
13.
The CCR runs automatically through the active steps
14.
When finished, press >C< shortly to end the Learn procedure
15.
Then press >
→
< for some sec. until the ”Store data menu” is shown
16.
Store the learned data by pressing >E<
17.
”Normal procedure” for LAME is finalized
Procedure for high accuracy
The accuracy from the Normal procedure can be improved by adding one or more ”break-points”:
Remove the number of lamps belonging to the actual “Break-point”
In User Menu 1 press >8< for ”Break-point”
Upon request enter the number of faulty lamps, meaning ”- XX lamps?”, where
XX is number of faulty lamps in the ”Break-point”, then press >E<
The CCR runs automatically through the active steps
When CCR is switched-off again, a new “Break-point” can be entered or
Press >C< shortly to end the ”Break-point” procedure
Press >
→
< some sec. until the ”Store data menu” is shown
Press >E< to store learned data
Содержание CCR 961-SW4.00
Страница 1: ...Regulator type CCR 961 SW4 00 USER MANUAL GB...
Страница 9: ...CCR961 MANUAL GB 9 Version B2 01 07 2015...
Страница 13: ...CCR961 MANUAL GB 13 Version B2 01 07 2015...
Страница 19: ...CCR961 MANUAL GB 19 Version B2 01 07 2015 CCR front view...
Страница 36: ...CCR961 MANUAL GB 36 Version B2 01 07 2015...