Components
The wind module monitors the wind turbine. It monitors voltage, current or
wind speed. Up to 4 Wind units can be implemented.
IOB
The IOB module enables access to data measured by the sensors and
actuators attached to the I/O panel of the Energy Manager and Extension
Boards. Up to 30 IOB modules can be implemented.
IOB4
The IOB4 module enables access to the data of measured by sensors
and actuators attached to the I/O panel of the Energy Manager. AIU
rules can be defined for the relay outputs available on the I/O board. The
port selection and calibration data for the analog inputs are stored in this
module. Up to 1 IOB4 module can be implemented. IOB4 is available
only for Energy Manager V 1.x.
IOM 3
The IOM3 module enables access to AIU rules that can be defined for the
relay outputs of the I/O board.
Up to 1 IOM3 can be implemented. IOM3 is available only for Energy
Manager V 1.x.
Free Cooling Unit Module (FCU)
The free cooling module controls the free cooling unit, which is used to
cool a shelter with ambient air. Indoor and outdoor temperature levels are
constantly compared. Up to 2 free cooling units can be implemented.
Fuel Cell Unit (FCunit)
The fuel cell unit module monitors data of a specific fuel cell unit such as
the generated power and alarms. Up to 4 fuel cell units can be
implemented.
Fuel Management (FUEL)
The diesel fuel management module monitors data related to the fuel tank
such as the measured tank level and related variables including fuel loss,
fuel refill, and total consumption. 1 Fuel tank can be implemented.
Genset Management (GEN)
The Genset management module controls the diesel generator.
Depending on the system status, the generator is switched on or off. In
order to increase Genset efficiency, maintenance, and reliability, the
runtime can be split between different generators. Up to 2 gensets can be
implemented.
Several generator state variables are monitored, including the starter
battery voltage, and variables dependent upon the generator controller
hardware such as the coolant level, coolant temperature, and oil
pressure. Optionally, a generator oil management system can be installed
and controlled.
20
Energy Manager 2.0 - Instruction Manual
Содержание Energy Manager 2.0
Страница 1: ...Energy Manager 2 0 Instruction Manual ...
Страница 6: ......
Страница 14: ......
Страница 78: ......
Страница 93: ...Energy Manager 2 0 Instruction Manual 93 ...
Страница 94: ......
Страница 101: ...Heliocentris Industry GmbH Rudower Chaussee 29 12489 Berlin Germany http www heliocentris com ...