7 Error Handling
46
Programmer PG 02
3071 ErrCanComm
3171 SErrCanComm
Cause:
There is an overrun in the destination buffer or a message cannot be fed into
CAN bus.
Response:
- Depending on the application.
Action:
- Check CAN module.
- Check CAN connection.
3075 ErrClearFlash
3175 SErrClearFlash
Cause:
Occurrence of an error on clearing the control's flash memory.
Response:
- Control cannot be put into operation.
- Emergency shutdown.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
3076 ErrParamStore
3176 SErrParamStore
Cause:
Occurrence of an error on programming the control's flash memory.
Response:
- Control cannot be put into operation.
- Emergency shutdown.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
3077 ErrProgramTest
3177 SErrProgramTest
Cause:
Current monitoring of the programme memory reports an error.
Response:
- Engine cannot be started.
- Emergency shutdown.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
3078 ErrRAMTest
3178 SErrRAMTest
Cause:
Current monitoring of the working memory reports an error.
Response:
- Engine cannot be started.
- Emergency shutdown.
Action:
- Note down the values of the parameters 3895
RAMTestAddrHigh
and
3896
RAMTestAddrLow
.