![Heinzmann Programmer 2 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/heinzmann/programmer-2/programmer-2_manual_2120038050.webp)
7 Error Handling
44
Programmer PG 02
3060 ErrAmplifier
3160 SErrAmplifier
Cause:
Overload, overtemperature at amplifier .
Response:
- Error message.
Actions:
- Restart governor by reset.
- Notify HEINZMANN.
Note:
These parameters are implemented only in the HELENOS series.
3060 ErrFeedbackAdjust2
3160 SerrFeedbackAdjust2
Cause:
Automatic calibration of the actuator 2 could not be performed, wrong input
of reference values for actuator.
Response:
- Governor cannot be put into operation.
Actions:
- Check voltage supply and supply lines to actuator 2.
- Check feedback cable to actuator 2.
- Check actuator 2, replace actuator 2 if necessary.
- Engine stop switch must be opened (indication parameter 2810
Switch-
EngineStop
= 0) to perform automatic calibration of actuator 2 with 2-
quadrant-operation.
- Check reference values and error limits for feeedback
- Programme feedback error limits
1962
FeedbackErrorLow
= 0
1963
FeedbackErrorHigh
= 65535
store values (
↑
, restart governor by reset
and repeat
automatic calibration.
- Set error limits again.
Note:
These parameters are implemented only in the PRIAMOS III series.
3061 ErrFeedbackAdjust3
3161 SerrFeedbackAdjust3
Cause:
Automatic calibration of the actuator 3 could not be performed, wrong input
of reference values for actuator.
Response:
- Governor cannot be put into operation.
Actions:
- Check voltage supply and supply lines to actuator 3.
- Check feedback cable to actuator 3.
- Check actuator 3, replace actuator 3 if necessary.
- Engine stop switch must be opened (indication parameter 2810
Switch-
EngineStop
= 0) to perform automatic calibration of actuator 3 with 2-