7 Error Handling
36
Programmer PG 02
Error Reason
3001
ErrPickup1
Error at pickup 1
3002
ErrPickup2
Error at pickup 2
3004
ErrOverspeed
Overspeedl
3031
ErrOilPressEcy
Oil pressure below speed dependent shutdown threshold
3050
ErrFeedback
Error at feedback of actuator 1
3051
ErrFeedback2
Error at feedback of actuator 2 (PRIAMOS III)
3052
ErrFeedback3
Error at feedback of actuator 3 (PRIAMOS III)
3056
ErrFeedbackRef
Error at feedback reference of actuator 1
3059
ErrFeedbackAdjust
Error at automatic actuator adjustment with actuator 1
3060
ErrFeedbackAdjust2
Error at auto. actuator adjust. with act. 2 (PRIAMOS III)
3061
ErrFeedbackAdjust3
Error at auto. actuator adjust. with act. 3 (PRIAMOS III)
3075
ErrClearFlash
Error at erasing the flash memory
3076
ErrParamStore
Error at saving of the parameters in flash memory
3077
ErrProgramTest
Error during permanent check of programme memory
3078
ErrRAMTest
Error during permanent check of RAM memory
3089
ErrWatchdog
Undefined programme flow, internal programming error
3090
ErrData
No parameters or check sum over parameters wrong
3091
ErrLogical
Error of parameter structure
3093
ErrStack
Stack overflow, internal programming error
3094
ErrIntern
Exception, internal programming error
7.4
Error Parameter List
The below error parameter list contains descriptions of the causes of each single error and
of the control's response. Furthermore, it lists the appropriate actions to be taken to remove
the respective error.
The errors are stored in the volatile error memory under the parameter numbers 3000 and
higher and (as far as provided) in the permanent error memory under the parameter
numbers from 3100 onward.
The errors are sorted by ascending numbers with the parameter on the left indicating the
actual error as stored in the volatile memory and with the parameter on the right indicating
the one stored as a sentinel in the permanent error memory. As explained above, the
control will only react to actual errors whereas the permanent error memory serves no
other purpose than to accumulate information on the occurrences of errors.