background image

5

Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

outdoors or spaces open to the outdoors. These 

include attics* and crawl spaces. Follow the National 

Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 

Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

*IMPORTANT:

 Do not provide openings for inlet or 

outlet into attic. If attic has a thermostat-controlled 

power vent, heated air entering the attic will activate 

the power vent.

IMPORTANT:

 Vent-free heaters add moisture to 

the air. Although this is beneficial, installing heater 

in rooms without enough ventilation air may cause 

mildew to form from too much moisture. See Fresh 

Air for Combustion and Ventilation, pages 3 

 

through 5. 

INSTALLATION

NOTICE:

 This heater is intended for the use as 

supplemental heat. Use this heater along with your 

primary heating system. Do not install this heater as 

your primary heat source. If you have a central heating 

system, you may run system’s circulating blower while 

using heater. This will help circulate the heat throughout 

the house. In the event of a power outage, you can use 

this heater as your primary heat source for the duration 

of the outage. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 

heater, Gas furnace, Vented gas heater, Gas 

fireplace logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and 

vents to the outdoors.
Example:
Gas water heater  40,000 Btu/hr
Vent Free   20,000 Btu/hr
Total 

 

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the   

 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined 

space because the actual Btu/hr used is more than 

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 

are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between the rooms. See Ventilation 

Air From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfined. 

If actual Btu/hr used is less than the maximum 

Btu/hr the space can support, the space is an 

unconfined space. You will need no additional fresh 

air ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 

space. When ventilation to an adjoining unconfined 

space, you must provide two permanent openings: one 

within 12” of the ceiling and one within 12” of the floor 

on the wall connecting the two spaces (see options 

1 & 2 of figure 2). You can also remove door into 

adjoining room (see option3, fig 2). Follow the National 

Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 

Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

 WARNING:

 Rework worksheet, adding the space 

of the adjoining unconfined space. The combined 

space must have enough fresh air to supply all 

appliance in both spaces. 

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation 

grills or ducts. Connect these items directly to the 

Ventilation 

Gills into 

Adjoining 

Room - Op-

tion 1

Ventilation Gills into Ad-

joining Room - Option 2

12”

12”

Or remove 

door into 

Adjoining 

Room - 

Option 3

INLET 

AIR

OUTLET 

AIR

VENTILATION CRAWL SPACE

TO CRAWL 

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 

ATTIC

OUTLET AIR

Figure 2

Figure 3.

Содержание HSSVFBF10LPT

Страница 1: ...ot use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Insta...

Страница 2: ...conversion is not permitted WARNING Do not use any accessory not approved for use with this heater WARNING Any change to this heater or its controls can be dangerous Do not place clothing or other fla...

Страница 3: ...r If heater keeps shutting off it requires servicing 5 Turn off and let cool before servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liqui...

Страница 4: ...maller than defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by the methods described in the National Fuel Gas Code...

Страница 5: ...space can support 60 000 Btu hr Actual amount of Btu hr used The space in the above example is a confined space because the actual Btu hr used is more than the maximum Btu hr the space can support You...

Страница 6: ...18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next...

Страница 7: ...s firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or masonry Note Wall anchors mounting scr...

Страница 8: ...NPT street elbow to make gas connection CAUTION Never connect heater directly to the Propane supply This heater requires an external regulator which is attached to the supplied hose Install the extern...

Страница 9: ...ipment shutoff valve see figure 12 2 Pressurize supply piping system by either using compressed air or opening propane LP supply valve 3 Check all joints from the propane LP supply valve to equipment...

Страница 10: ...smell gas STOP Follow B in the safety information above If you do not smell gas go to the next step 5 Push in gas control know slightly and turn counterclockwise to PILOT IGN and depress for five 5 se...

Страница 11: ...p the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 psig This can be done by using a vacuum cleaner in the bl...

Страница 12: ...Replace thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Clean burner...

Страница 13: ...ng Gas Connections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing a...

Страница 14: ...ocouple LP 1 21 80019 Ignitor Pulse 1 8 80017 Burner Assembly 1 22 80014 Ignitor Wire 1 9 80009 Orifice 1 23 8001 1 Ignitor Bracket 1 10 N A Burner Right Bracket 1 24 80010 Thermostat Valve Mounting B...

Страница 15: ...DESCRIPTION QTY 1 80040 Wire Guard 1 1 1 N A Regulator Connection 1 2 80051 Front Panel 1 12 80058 Floor Mounting Feet 1 3 80024 Reflector 1 13 80052 Back Panel 1 4 80030 Burner Assembly 1 14 80036 Wa...

Страница 16: ...00 PM EST Monday through Friday Please include the model number date of purchase serial number and description of problem in all communication LIMITED WARRANTY Enerco Group Inc EGI warrants Heatstar...

Отзывы: