Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

WARNING:

 Never use an open flame to check for 

a gas leak. Apply a mixture of liquid soap and water 

to all joints. Bubbles forming show a leak. Correct 

all leaks at once. 

PRESSURE TESTING GAS SUPPLY PIPING 

SYSTEM
High Pressure 

Test pressure in Excess of ½ psig (3.5kPa)

1.  Disconnect appliance with its appliance main 

gas valve (control valve) and equipment shutoff 

valve from gas supply piping system. Pressures 

in excess of ½ psig will damage heater regulator.

2.  Cap off open end of gas pipe where equipment 

shutoff valve was connected.

3.  Pressurize supply piping system by either using 

compressed air or opening main gas valve on 

or near gas meter.

4.  Check all connections and joints in gas supply 

piping system. Apply mixture of liquid soap and 

water to gas joints. Bubbles forming show a 

leak.

5.  Correct all leaks at once.
6.  Depressurize and relieve pressure in supply 

piping system.

7.  Reconnect heater and equipment shutoff valve 

to gas supply. 

8.  Reconnected fittings must be checked for leaks 

in next section. 

Low Pressure

Test Pressure Equal To or Less Than ½ psig (3.5 kPa)

1.  Close equipment shutoff valve (see figure 12).
2.  Pressurize supply piping system by either using 

compressed air or opening propane/LP supply 

valve.

3.  Check all joints from the propane/LP supply 

valve to equipment shutoff valve (see figure 

13). Apply mixture of liquid soap and water to 

gas joints. Bubbles forming show a leak.

4.  Correct all leaks at once.
5.  Depressurize and relieve pressure from supply 

piping system.

Pressure Testing Heater Gas Connections:

1.  Make sure that the heater supply piping sys

-

tem is connected and has been leak tested as 

described above.

2.  Make sure control knob of heater is in OFF 

position.

3.  Open equipment shutoff valve (see figure 12). 
4.  Open propane/LP supply valve.
5.  Check all joints from equipment shutoff valve 

to control valve (see figure 13). Apply mixture 

of liquid soap and water to gas joints. Bubbles 

forming show a leak.

6.  Correct all leaks at once.
7.  Light heater (see 

Operating Your Heater

, page 10.

8.  Turn off heater (see 

To Turn OFF Gas to 

Appliance

, page 10. 

9.  Replace lower front panel. 

Equipment 

Shutoff Valve

Open

Closed

FIGURE 12

FIGURE 13

FIGURE 14

Nipple

Tee Joint

Cap

Shutoff Valve

HEATER CABINET

Nipple

Nipple

Tee Joint

Ground Joint Union

3/8” NPT Pipe Nipple

Pressure 
Regulator

Test Gauge
Connection

1/8” NPT Plug Tap

Reducer Bushing
to 1/8” NPT

Nipple

Sediment 
Trap

3” minimum

Fuel line from 

Regulated LP Tank

(11”W.C to 14” WC Pressure)

Содержание HSSVFBF10LPT

Страница 1: ...ot use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Insta...

Страница 2: ...conversion is not permitted WARNING Do not use any accessory not approved for use with this heater WARNING Any change to this heater or its controls can be dangerous Do not place clothing or other fla...

Страница 3: ...r If heater keeps shutting off it requires servicing 5 Turn off and let cool before servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liqui...

Страница 4: ...maller than defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by the methods described in the National Fuel Gas Code...

Страница 5: ...space can support 60 000 Btu hr Actual amount of Btu hr used The space in the above example is a confined space because the actual Btu hr used is more than the maximum Btu hr the space can support You...

Страница 6: ...18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next...

Страница 7: ...s firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or masonry Note Wall anchors mounting scr...

Страница 8: ...NPT street elbow to make gas connection CAUTION Never connect heater directly to the Propane supply This heater requires an external regulator which is attached to the supplied hose Install the extern...

Страница 9: ...ipment shutoff valve see figure 12 2 Pressurize supply piping system by either using compressed air or opening propane LP supply valve 3 Check all joints from the propane LP supply valve to equipment...

Страница 10: ...smell gas STOP Follow B in the safety information above If you do not smell gas go to the next step 5 Push in gas control know slightly and turn counterclockwise to PILOT IGN and depress for five 5 se...

Страница 11: ...p the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 psig This can be done by using a vacuum cleaner in the bl...

Страница 12: ...Replace thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Clean burner...

Страница 13: ...ng Gas Connections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing a...

Страница 14: ...ocouple LP 1 21 80019 Ignitor Pulse 1 8 80017 Burner Assembly 1 22 80014 Ignitor Wire 1 9 80009 Orifice 1 23 8001 1 Ignitor Bracket 1 10 N A Burner Right Bracket 1 24 80010 Thermostat Valve Mounting B...

Страница 15: ...DESCRIPTION QTY 1 80040 Wire Guard 1 1 1 N A Regulator Connection 1 2 80051 Front Panel 1 12 80058 Floor Mounting Feet 1 3 80024 Reflector 1 13 80052 Back Panel 1 4 80030 Burner Assembly 1 14 80036 Wa...

Страница 16: ...00 PM EST Monday through Friday Please include the model number date of purchase serial number and description of problem in all communication LIMITED WARRANTY Enerco Group Inc EGI warrants Heatstar...

Отзывы: