Heat & Glo • FDN-4-SS, FDN-5-SS, FDN-6-SS, FDN-7-SS Installation Manual • 16400-9800 Rev. H • 11/19
36
10 - FINISHING
A. FINISHING THE WALL - USING THE PROVIDED 1/2" STANDOFFS
NOTE:
DO NOT
PIERCE ANY OF THE BLACK PAINTED SURFACES WITH SCREWS, RIVETS, ETC.
THIS INCLUDES THE 3" BLACK TOP AND BOTTOM GLASS TRIM AND ANY PAINTED SIDES ADJACENT TO THE GLASS.
NOTE: REFER TO DIMENSIONS SECTION FOR ALLOWABLE FINISHING DIMENSIONS REQUIRED TO FIT THE GLASS
PANELS INTO THE FIREPLACE. FINISHING MATERIALS MUST NOT OVERLAP THE FRAMING DIMENSIONS REFERENCED
IN SECTION 2.A. NEVER COVER THE GLASS WITH FINISHING MATERIALS.
NOTE: REFER TO MANTEL REQUIREMENTS: NON-COMBUSTIBLE ZONE USING PROVIDED 1/2" STANDOFFS FOR MORE
INFORMATION (SECTION 5A).
Figure 10A.1
WARNING! Risk of Fire!
DO NOT apply combustible materials beyond the minimum clearances.
Comply with all minimum clearances to combustibles as specifi ed in this manual.
IMPORTANT: NEVER COVER THE GLASS WITH FINISHING MATERIALS
E - COMBUSTIBLE
MANTEL
F - COMBUSTIBLE
HEARTH
G. ACCESS PANEL
SINGLE SIDED FIREPLACE SHOWN:
APPLIES TO BOTH SIDES AND ENDS IF
USING A MULTI-SIDED FIREPLACE
I. COMBUSTIBLE FRAMING
AND FINISHING MATERIAL
3” TOP TRIM
STANDOFF
REFER TO (B)
D - COMBUSTIBLE OR NON-COMBUSTIBLE
BACKER MATERIAL (I.E. SHEETROCK)
C - COMBUSTIBLE OR NON-COMBUSTIBLE
FINISHING MATERIAL
COMBUSTIBLE FRAMING
A
B
A. No combustible materials may be within 6” [152mm] of the top of the fireplace.
B. 1/2” [12.7] CLEARANCE TO COMBUSTIBLES ON SURFACE. The fireplace ships with standoffs in place to ensure a 1/2” clearance to
combustibles is maintained on the surface. See Figure 10A.1. If the standoffs are removed, only non-combustible material can be installed against
the surface of the fireplace such as a non-combustible backer cement board. 1/2” [12.7mm] minimum thickness must be used in the 15” [381mm]
between the top of the 3’’ trim to the combustible framing the full width of the fireplace. The 15” includes a 7” [178mm] minimum above above the top of
the fireplace that is recommended for ease of attachment. See Figure 10A.2
C. Combustible material may cover the non-combustible area mentioned in B.
D. Combustible finishing materials allowed.
E. Combustible or Non-Combustible mantel may be placed above the top of the glass viewing area. There are no restrictions on mantel depth.
F. Combustible hearth may be placed below the bottom of the glass viewing area.
G. Flat covers will cover the components access. Gas and electric inlets are located behind this panel. There are four access panel options all
located on the pilot side of the fireplace; front (shown above), side, back and inside behind the glass.
Please take consideration of which option will be used to access the components for service later during planning.
I. Combustible framing and finishing materials allowed.